IntRoduCtIon
Product Specications Summary
1.1 Power Supply
Transformer Input: Model 327, plug-in — Primary input: 120 VAC, 60 Hz, Secondary output: 16.5 VAC 50 VA
Model 322, wire-in — Primary input: 120 VAC, 60 Hz, Secondary output: 16 VAC 56 VA
Standby Battery: 12 VDC, 1.0 Amps Max. charging current
Models 365, 366, 367, 368, or 369
Replace every 3 to 5 years
* Auxiliary: 12 VDC output at 1.5 Amp Max
* Bell Output: 12 VDC at 1.5 Amp Max
Note: The combined Auxiliary and Bell outputs total cannot exceed 3 Amps with a 50 VA or 56 VA Transformer.
All circuits are inherent Power Limited except the red battery wire and AC terminal.
* For Commercial Fire installations, see the Compliance Instructions section.
1.2 Communication
Built-in network communication to DMP Model SCS-1R Receivers (XR500N/XR500E only)
Built-in encrypted communication to iCOM-E™ Encrypted Network Alarm Router (XR500E only)
Built-in dialer communication to DMP Model SCS-1R Receivers
Built-in Contact ID communication to non-DMP receivers
Optional 893A Dual Phone Line Module with phone line supervision
Can operate as a local panel
1.3 Panel Zones
Eight 1k Ohm EOL burglary zones (zones 1 to 8)
Two 3.3k Ohm EOL powered zone with reset (zones 9 and 10)
1.4 Keypad Bus
You can connect up to 16 of the following supervised keypads and expansion modules to the keypad bus:
• Alphanumerickeypads • Four-and/orsingle-zoneexpansionmodules
• Single-zonedetectors • Accesscontrolmodules
1.5 LX-Bus™
You can connect the following devices to the LX-Bus™ provided on the panel or by the DMP 481, 462N, 462P and 472
Interface Cards up to the maximum number of LX-Bus™ addresses. See Accessory Devices in section 3.4.
• Four-and/orsingle-zoneexpansionmodules • Single-zonedetectors
• Relayoutputexpansionmodules • Graphicannunciatormodules
1.6 Outputs
The XR500 Series provide two Single Pole, Double Throw (SPDT) relay outputs which require the installation of two
Model 305 relays, each rated 1 Amp at 30 VDC resistive (power limited sources only). A Model 431 Output Harness is
required to use these outputs.
The XR500 Series panels also provide four open collector outputs rated for 50mA each. The open collector outputs
provide ground connection for a positive voltage source. A Model 300 Output Harness is required to use these
outputs.
1.7 Enclosure Specications
The XR500 Series panels are shipped in an enclosure with a transformer, End-of-Line resistors, battery leads, user’s
guide, and programming sheets.
Enclosure
Model
Size Color(s) Construction (Cold Rolled
Steel)
350 17.5”W x 13.5”H x 3.5”D Gray (G) or Red (R) 18-Guage
350A 17.5”W x 13.5”H x 3.75”D Gray (G) 18-Guage with 16-Guage door
341 12.75”W x 6.55”H x 2.9”D Gray (G) 20-Guage
352X 14.5”W x 32.0”H x 4.0”D Gray (G) 16-Guage