Installation guide
Digital Monitoring Products XR500 Series Installation Guide
52
WIRInG dIaGRams
37.15 Derived Channel Installation Using Bosch D8122
J6
Interface
Card
Expansion
Connector
Output Header J2 for K6 and K7 Dry Contact
Relays. All outputs must be connected to devices
located within the same room as the panel.
XR500 Series Command Processor™ Panel
AC
12345678 10 11 12 13 14 15 16 17 18 199202122232425262728
+B BELL GNDSMK GNDRED YEL GRNBLK Z1 Z2 Z3 Z4 Z5 Z6 Z7 Z8 Z9+Z9– Z10+Z10–AC –B GNDGND GNDGND
K6
K7
J3
Phone Line
J10
J22
Battery
Start
J23
J21
J8
PROG
J4
Tamper
J16
Reset
J11
J2
J1
Telco Jack
R
L
X
1 2 3 4 5 6 7 8
OPEN
1 2 3 4 5 6 7 8
OPEN
SW1 (MSB) SW2 (LSB)
P1
J1
J2
P2
1 2 3
JP4
1 2 3
JP3
1 2 3
JP1
1 2 3
JP2
+ 12V
+12 VDC Out
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
CONT OUT
COMM
Output 2 Common Wire
Output 1 Common Wire
D8122
Form C Dry Contact Relays (J2)
Output Color Code–Model 431 Harness
Output 2 N/O Orange/White
Output 2 Com White/Gray
Output 2 N/C Violet/White
Output 1 N/O Orange
Output 1 Com Gray
Output 1 N/C Violet
Panel Terminal 7 Wire
Panel Common Wire
Interfacing D8122 to the XR500 Series Panels
TheD8122mayonlybeusedinconjunctionwithtelephonesystemsthatsupportDerivedChannelnetwork.For
installationinstructions,seetheDerivedChannelSTUD8121A/D8122OperationandInstallationGuide.
• ForStandardLineSecurityapplications,thepanelmustbeinstalledandprogrammedtomeetburglaryalarm
system requirements.
• ThepanelmustbeinstalledandprogrammedforreportingallalarmconditionsthroughtheintegralDACTor
network connection to the same central station that monitors the D8122.
• TheD8122mustbeinstalledinthesameenclosureastheXR500Seriespanelusingthesuppliedmounting
hardware.RefertotheSTUD8121A/D8122OperationandInstallationGuide.
• DerivedChannelCommunicationisnotapplicableforULCCanadianInstallations.