WIRInG dIaGRams
37.12 Panel Slave Communicator for FACP using 630F Annunciator
Main Fire Alarm
Control Panel (FACP)
{
{
{
Normally Open
Common
Normally Closed
Normally Open
Normally Open
Common
Common
Normally Closed
Normally Closed
1.0k Ohm
1k Ohm EOL
1.0k Ohm
Fire Alarm
Form C alarm contacts activate
short on General Fire Alarm.
General Trouble
Form C trouble contacts activate
open on General Trouble.
General Trouble must not be
used to indicate AC power fail
unless it can be delayed at least
1 hour.
Supervisory
Form C contacts activate short on
Supervisory condition.
AC
12345678 10 11 12 13 14 15 16 17 18 199202122232425262728
+B BELL GND SMK GNDRED YEL GRN BLKZ1Z2Z3Z4Z5Z6Z7Z8 Z9+ Z9- Z10+ Z10-AC -B GND GND GNDGND
K6 K7
Output 1
Output 2
J3
Phone Line
J10
J22
LX-Bus
Battery
Start
J23
J21
RS-232
Power LED
J8
PROG
J4
Tamper
Out2
J11
3
4
5
6
J2
J1
Ethernet
POWER
TROUBLE
ALARM
COMMAND
1234
5678
90
ABC DEF GHI JKL
MNOPQR STU VWX
YX
ENABLE
SILENCE
RESET
TEST
DRILL
Fire Command Center
630F Annunciator
Standy
Batteries
To 322/323
transformer
Must be connected
to same circuit
as FACP
Model 311
1K EOL
Zone 3
Zone 4
Zone 6
XR500 Series
Command Processorâ„¢ Panel
Program forFire Protective Signaling communication to the
Central Station.
Program Fire Alarm zone as type FI and set Fire Panel Slave
Input option as YES.
Program General Trouble zone as type FI.
Program Supervisory zone as type SV and set the Latch
Supervisory option in System Options as NO.
Program Bell Options
fire type as None.