Installation guide
XR500 Series Installation Guide Digital Monitoring Products
35
ComPlIanCe
32.4 Bell Cutoff
TheBellCutofftimecannotbelessthanveminutes.
32.5 Detect Wireless Jamming
The Detect Wireless Jamming option must be programmed YES.
32.6 Wireless External Contact
When used, the External Contact of 1101 or 1102 must be programmed Normally Closed.
32.7 Wireless Supervision Time
The Zone Information Supervision Time must be 240 minutes.
32.8 Wireless Fire Verication
Whenused,theModel1161and1162wirelesssmokedetectorsmustnotbeprogrammedasFireVerication(FV)
zone type.
California State Fire Marshal Specications
33.1 Bell Output Denition
The Model XR500 Series panel Bell Output must be programmed to operate steady on burglary alarms and pulsed,
temporal,orCaliforniaSchoolCodeonrealarms.
New York City (MEA) Specications
34.1 Introduction
Theprogrammingandinstallationspecicationscontainedinthissectionmustbecompletedwheninstallingthe
XR500SeriespanelforNewYorkCity(MEA)realarminstallationsthatprovideadigitaldialerwithnetworkIP
communicationasbackup.Firealarminstallationsthatusetwodigitaldialertelephonelinesdonotneedtocomply
withthesespecications.
34.2 Digital Dialer and Network Communication
Whenusedwithacentralofcecommunicatororatransmitter,theinstallationandoperationoftheequipmentand
devices shall comply with 3RCNY 17-01. The installation shall employ the digital dialer as the primary communicator
(using telephone line) with network IP communication as backup or secondary means of communication. It shall
have the capability of transmitting separate and distinct signals to indicate manual pull station alarm, automatic
detectionalarm,sprinklerwaterowalarm,supervisorysignalindicationsandtroubleindications.
34.3 Wiring
AllwiringmustbeinaccordancewithNEC,ANSI,andNFPA70.Allnetworkcablingmustbeinstalledinaccordance
withNFPA70forcommunicationcircuits.
34.4 Communication Programming
Fordigitaldialercommunicationwithsupervisednetworkbackup,programthefollowing:
PRIMARY COMM TYPE = DD
FIRSTPHONENUMBER=CentralStationReceiverPhoneNumber
BACKUP COMM TYPE = NET
RECEIVER
ALARMS = YES
34.5 Additional Requirements
ProgramandinstalltheequipmenttocomplywithNFPAbasicrerequirements.RefertotheUniversalFireAlarm
SpecicationsandANSI/UL864NFPA72Specicationsinthisdocument.