Installation guide

XR500 Series Installation Guide Digital Monitoring Products
35
ComPlIanCe
32.4 Bell Cutoff
TheBellCutofftimecannotbelessthanveminutes.
32.5 Detect Wireless Jamming
The Detect Wireless Jamming option must be programmed YES.
32.6 Wireless External Contact
When used, the External Contact of 1101 or 1102 must be programmed Normally Closed.
32.7 Wireless Supervision Time
The Zone Information Supervision Time must be 240 minutes.
32.8 Wireless Fire Verication
Whenused,theModel1161and1162wirelesssmokedetectorsmustnotbeprogrammedasFireVerication(FV)
zone type.
California State Fire Marshal Specications
33.1 Bell Output Denition
The Model XR500 Series panel Bell Output must be programmed to operate steady on burglary alarms and pulsed,
temporal,orCaliforniaSchoolCodeonrealarms.
New York City (MEA) Specications
34.1 Introduction
Theprogrammingandinstallationspecicationscontainedinthissectionmustbecompletedwheninstallingthe
XR500SeriespanelforNewYorkCity(MEA)realarminstallationsthatprovideadigitaldialerwithnetworkIP
communicationasbackup.Firealarminstallationsthatusetwodigitaldialertelephonelinesdonotneedtocomply
withthesespecications.
34.2 Digital Dialer and Network Communication
Whenusedwithacentralofcecommunicatororatransmitter,theinstallationandoperationoftheequipmentand
devices shall comply with 3RCNY 17-01. The installation shall employ the digital dialer as the primary communicator
(using telephone line) with network IP communication as backup or secondary means of communication. It shall
have the capability of transmitting separate and distinct signals to indicate manual pull station alarm, automatic
detectionalarm,sprinklerwaterowalarm,supervisorysignalindicationsandtroubleindications.
34.3 Wiring
AllwiringmustbeinaccordancewithNEC,ANSI,andNFPA70.Allnetworkcablingmustbeinstalledinaccordance
withNFPA70forcommunicationcircuits.
34.4 Communication Programming
Fordigitaldialercommunicationwithsupervisednetworkbackup,programthefollowing:
PRIMARY COMM TYPE = DD
FIRSTPHONENUMBER=CentralStationReceiverPhoneNumber
BACKUP COMM TYPE = NET
RECEIVER
ALARMS = YES
34.5 Additional Requirements
ProgramandinstalltheequipmenttocomplywithNFPAbasicrerequirements.RefertotheUniversalFireAlarm
SpecicationsandANSI/UL864NFPA72Specicationsinthisdocument.