Installation guide

Digital Monitoring Products XR500 Series Installation Guide
34
ComPlIanCe
31.9 Combination Systems
Forcombinationreandburglarysystems,poweredburglarydevices(PIR,Glassbreak,etc.)mustbepoweredfroma
separate listed power supply (DMP Model 505-12). This requirement is not needed for non-powered burglary devices
(door contacts, etc.) which only connect to the zone input of zone expanders or keypads. Refer to Powered Burglary
Devices later in this document.
Forcombinationreandburglarysystems,burglarysoundingdevicessuchassirensandbellsmustbeenergized
using panel relays, 860 relays, or 716 relays. Programming the output to activate the relay must occur using the
Burglary Bell Output option in Area Information or by the Alarm Action output option of Zone Information. The
Burglary Bell Action option of the panel Bell Options must be programmed as None.
31.10 Remote Annunciators
AtleastoneModel630FRemoteAnnunciatormustbeusedonthesystem.Allrealarms,retroublesand
supervisoryalarmsortroublesmustbeannunciatedonlyonthe630F.Allburglaryalarmsortroublesmustonlybe
annunciatedonnon-rekeypads.SeeStatusListoptionsoftheXR500SeriesProgrammingGuide(LT-0679).
31.11 Notication Appliances
ThefollowingtableindicatestheapprovednoticationappliancesthatcanbeusedwiththeXR500Seriessystem.
Wheelock Model No. Description Max No. of Appliances using 56 VA
MT-12/24 Multi-tone Horn 8
MB-G6-12 Bell, 6 inch 16
MB-G10-12 Bell, 10 inch 16
RSS-121575W-F Strobe, 15/75 candela 5
RSSP-121575W-F Strobe,w/retrotplate 5
NS-121575W-F Horn Strobe, 15/75 candela 5
SM-12/24-R Sync Module, Single circuit
DSM-12/24-R Sync Module, Dual circuit
31.12 Cross Zoning
When using cross zoning, there must be a minimum of two detectors installed in each protected space and the
detectorinstallationspacingmustbe0.7timesthelinearspacinginaccordancewithNationalFireAlarmCode,
NFPA72.
31.13 Ground Fault
Forsupervisedcircuits,groundfaultisdetectedat0(zero)Ohms.
31.14 Wireless Testing
Whenusingthe1100XWirelessReceiverforFireProtectiveSignaling,afteralltransmittersareinposition,theWLS
optionofthepanel’sWalkTestmustbeoperatedandalltransmittersprogrammedforFire(FI)orSupervisory(SV)
must show that their checkin message was received.
Household Fire Warning System Units
ANSI/UL 985, NFPA 72
32.1 Bell Output Denition
The Model XR500 Series panel Bell Output must be programmed to operate steady on burglary alarms and pulsed or
temporalonrealarms.
32.2 Audible Devices
At least one listed audible device rated to operate over the voltage rate of 11.7 VDC to 12.8 VDC and rated at 85 DB
minimum must be used.
32.3 Auxiliary Circuits
Atleastonerealarminitiatingdeviceshallbeusedonthesystem.Ifthevoltageforthedeviceisappliedbythe
controlunittherealarminitiatingdeviceshallberatedtooperateovertherangeof11.5VDCto12.7VDC.