31.6 Local Protective Signaling Systems
TheDMPModel865,866,or867NoticationCircuitModulemustbeusedonthebellcircuitfordetectionofshorts
and grounds. Any burglary or other off premises communication must be done with the Model 893A Dual Phone Line
Module.Forlocalcommercialreinstallations,the893Aisrequired.
31.7 Remote Station Protective Signaling Systems
You must provide 60 hours of standby battery. See section 6.9 in this guide for standby battery calculations. Two
Radionics Model D127 Reversing Relay Modules provide two reversing polarity telephone connections. See the D127
Installation Instruction sheet for wiring details. A DMP Model 893A is used to provide two line dialer communication.
31.8 Fire Protective Signaling Systems using Internet/Intranet/Cell Networks
AnOtherTransmissionTechnologiessystemasdenedinUL8649thEdition,Section40.7maybeconguredasNET
PrimaryusingahardwireIPnetworkorCELLPrimaryusingaModel463GDigitalCellularCommunicatorwithor
withoutabackuppath.Thesystemmaybeconguredasoneofthefollowing:
Path 1 Type NET or CELL Primary with no Backup
Path 1 Programming
Comm Type = NET or CELL Checkin Min = 3
Path Type = Primary FailtimeMin=5
Test Rpt = No Sub Code = Yes
Checkin = Yes Send Comm Trbl = Yes
Path 1 Type NET Primary and Path 2 Type DD Backup
Path 1 Programming Path 2 Programming
Comm Type = NET Comm Type = DD
Path Type = Primary Path Type = Backup
Test Rpt = Yes Test Rpt = Yes
TestFreq=1Dy TestFreq=1Dy
Send Comm Trbl = Yes Send Comm Trbl = Yes
Comm Path Trbl = Yes (Status List Programming)
Path 1 Type NET Primary and Path 2 Type CELL Backup
Path 1 Programming Path 2 Programming
Comm Type = NET Comm Type = CELL
Path Type = Primary Path Type = Backup
Test Rpt = Yes Test Rpt = Yes
TestFreq=1Dy TestFreq=1Dy
Send Comm Trbl = Yes Send Comm Trbl = Yes
Comm Path Trbl = Yes (Status List Programming)
Path 1 Type CELL Primary and Path 2 Type NET Backup
Path 1 Programming Path 2 Programming
Comm Type = CELL Comm Type = NET
Path Type = Primary Path Type = Backup
Test Rpt = Yes Test Rpt = Yes
TestFreq=1Dy TestFreq=1Dy
Send Comm Trbl = Yes Send Comm Trbl = Yes
Comm Path Trbl = Yes (Status List Programming)