ComPlIanCe
Control Units for Fire-Protective Signaling Systems
ANSI/UL 864, NFPA 72
31.1 Power Supply
For listed installations, the total current combined from Auxiliary and Bell Power cannot exceed:
1.2 Amps with a 56 VA transformer; .5 Amp Max for Auxiliary Power and .7 Amp Max for Bell
Forlistedinstallations,the50VAPlug-intransformercannotbeused.
The total combined current from Terminals 7, 11, 25, and 27 cannot exceed 1.2 Amps.
31.2 Zone Restoral Reports
The Restoral Reports option must be selected as YES or Disarm.
31.3 Power Fail Delay
ThePowerFailDelayoptionmustbeselectedasrequiredbytheserviceofthepanel.ForCentralStationorRemote
Station service: 1.
31.4 Sprinkler Supervisory
Anyzoneusedforsprinklersupervisorymustbeprogrammedwith“SPRINKLRXXX”asthezonename.Thelastthree
characters in the zone name may be assigned a number to identify the zone. The Model 893A Dual Phone Line Module
must be used on all sprinkler supervisory systems.
31.5 DACT Systems
ADACTsystemmaybeconguredasoneofthefollowing:
Path 1 Type DD Primary and Path 2 Type DD Backup
Path 1 Type DD Primary and Path 2 Type CELL Backup
Path 1 Type DD Primary and Path 2 Type NET Backup
Path 1 Type DD Primary and Path 2 Type DD Backup
Use two telephone lines and the Model 893A Dual Phone Line Module to provide two phone line connections to the
system. Two different telephone numbers must be programmed for digital communication. Do not connect to
ground start or party lines.
Path 1 Programming Path 2 Programming
Comm Type = DD Comm Type = DD
Path Type = Primary Path Type = Backup
Test Rpt = Yes Test Rpt = Yes
TestFreq=1Dy TestFreq=1Dy
893A = Yes
Path 1 Type DD Primary and Path 2 Type CELL Backup
WhenusingatelephonelineandaGSMcellularasbackup,
Path 1 Programming Path 2 Programming
Comm Type = DD Comm Type = CELL
Path Type = Primary Path Type = Backup
Test Rpt = Yes Test Rpt = Yes
TestFreq=1Dy TestFreq=1Dy
Receiver IP Address
FirstGPRSAPN
Path 1 Type DD Primary and Path 2 Type NET Backup
When using a telephone line and a Network IP as backup,
Path 1 Programming Path 2 Programming
Comm Type = DD Comm Type = NET
Path Type = Primary Path Type = Backup
Test Rpt = Yes Test Rpt = Yes
TestFreq=1Dy TestFreq=1Dy
Receiver IP Address