Universal Fire Alarm Specications
30.1 Introduction
Theprogrammingandinstallationspecicationscontainedinthissectionmustbecompletedwheninstallingthe
ModelXR500SeriesinaccordancewithanyoftheANSI/ULorNFPArestandards.Additionalspecicationsmaybe
requiredbyaparticularstandard.SeetheXR500SeriesProgrammingGuide(LT-0679).
30.2 Wiring
AllwiringmustbeinaccordancewithNEC,ANSI/NFPA70.
30.3 Transformer
Use the Model 322 or 323 wire-in 16 VAC 56 VA transformer mounted within 20 feet of the panel and connected by
conduit.
30.4 End-of-Line Resistor
TheDMPModel3101kOhmEOLresistorshouldbeusedonall1kOhmEOLrezones.
30.5 System Trouble Display
The Status List Display must include at least one keypad that displays system monitor troubles.
30.6 Fire Display
TheStatusListDisplaymustincludeatleastonekeypadthatdisplaystroublesandalarmsonretypezones.
30.7 Police Station Phone Number
The digital dialer telephone number programmed for communication must not be a police station phone number,
unlessthatphonenumberisspecicallyprovidedforthatpurpose.
30.8 System Maintenance
To ensure continuous satisfactory operation of any alarm system, proper installation and regular maintenance by the
installing alarm company and frequent testing by the end user is essential. Offering a maintenance program and
acquainting the user with the correct procedures for system use and testing is also the responsibility of the installing
alarm company.
30.9 Audible Alarm
FireTypezonesmustbeprogrammedtoactivateanaudiblealarm.TheBellActionforFireTypezonesmustnotbe
programmed as N (None).
30.10 Fire Zone Programming
Ifaretarddelayisusedonawaterowzone,itcannotexceed90secondsandanyretarddelayinthewaterow
initiating devices must be subtracted from the 90 seconds al lowed. The retard delay should not be used on a zone
with smoke detectors.
30.11 Class A Style D Zones
If required, the DMP 869 Dual Style D Initiating Module provides for connection of two Class A Style D zones to the
ModelXR500Series.Seethe869InstallationGuide(LT-0186)andthisguideforwiringinformation.
30.12 Listed Receivers
UsetheDMPSCS-1R(SDLC),Sur-GardSG-HLR2-DG(CID),FBIICP220PB(CID),andOsborne-HoffmanQuick-Alert(CID)
receivers.