Listed Compliance Specications
20.1 Introduction
ForapplicationsthatmustconformtoalocalauthoritiesinstallationstandardoraNationalRecognizedTesting
Laboratorycerticatedsystem,pleaseseethefollowingsections.
Universal Burglary Specications
21.1 Introduction
Theprogrammingandinstallationspecicationscontainedinthissectionmustbecompletedwheninstallingthe
XR500Seriespanelinaccordancewithanyoftheburglarystandards.Additionalspecicationsmayberequiredbya
particularstandard.SeetheXR500SeriesProgrammingGuide(LT-0679).
21.2 Wiring
AllwiringmustbeinaccordancewithNEC,ANSI/NFPA70,ANSI/UL681,andANSI/UL827forallburglary
installations.
21.3 Control Outside of Protected Area
A Potter EVD or Sentrol 5402 should be used in place of a lined cabinet when the panel is installed outside of the
protectedarea.Frontandreartamperswitchesarerequired.Refertothesystemwiringdiagram.
21.4 Police Station Phone Numbers
The digital dialer telephone number programmed for communication must not be a police station phone number.
21.5 Bypass Reports
The Bypass Reports option must be programmed as YES for all listed burglary applications.
21.6 System Maintenance
To ensure continuous satisfactory operation of any alarm system, proper installation and regular maintenance by the
installing alarm company and frequent testing by the end user is essential. Offering a maintenance program and
acquainting the user with the correct procedures for system use and testing is also the responsibility of the installing
alarm company.
21.7 Listed Receivers
OperationhasbeenveriedwiththeDMPSCS-1R,Sur-GardSG-HLR2-DG,FBIICP220PB,Osborne-HoffmanQuick-
Alert, and Radionics D6500 receivers. It is the installer’s responsibility to verify compatibility between the XR500
Series and the receiver used during installation. The installer shall verify the compatibility of the receiver and the
system on a yearly basis.
21.8 Power Supply Supervision
Forcommercialburglaryapplicationsthepowersupplyforalllocalbellsshallbeunder24-hourprotection.Referto
the Secondary Power Supply section in this document.
21.9 Wireless Tamper
The Zone Information Disarmed Open Message to Transmit must be programmed Trouble (T). (Not applicable to
ANSI/UL 1023).
21.10 Wireless External Contact
When used, the External Contact of 1101 or 1102 must be programmed Normally Closed.
21.11 Wireless Supervision Time
The Zone Information Supervision Time cannot be set to 0 (zero).
21.12 Detect Wireless Jamming
The Detect Wireless Jamming option must be programmed YES. (Not applicable to ANSI/UL 1023).