Installation guide
XR500 Series Installation Guide Digital Monitoring Products
11
InstallatIon
6.8 XR500 Series Power Requirements
During AC power failure, the XR500 Series panel and all connected auxiliary devices draw their power from the
battery. All devices must be taken into consideration when calculating the battery standby capacity. The following
table lists the XR500 Series panel power requirements. You must add the additional current draw of keypads, zone
expansion modules, smoke detector output, and any other auxiliary devices used in the system for the total current
required. The total is then multiplied by the number of standby hours required to calculate the total ampere-hours
required.
Standby Battery Power Calculations Standby Current Alarm Current
XR500 Series Control Panel
Relay Outputs 1-2 (ON)
Switch Grounds 3-6 (ON)
Active Zones 1-8
Active Zones 9-10
2-Wire Smoke Detectors
Panel Bell Output
Qty 1 _
Qty _______
Qty _______
Qty _______
Qty _______
Qty _______
x 180mA
30mA
5mA
1.6mA
4mA
0.1mA
180 mA
______
______
______
______
______
Qty 1 _
Qty _______
Qty _______
Qty _______
Qty _______
Qty _______
x 180mA
30mA
5mA
*2mA
30mA
0.1mA
1500mA
180 mA
______
______
______
______
______
______mA
893A Dual Phone Line Module Qty _______ x 12mA ______ Qty _______ x 50mA ______
461 Interface Adaptor Card 7mA ______ 7mA ______
462N Network Interface Card Qty _______ x 50mA ______ Qty _______ x 50mA ______
462P Printer Interface Card Qty _______ x 50mA ______ Qty _______ x 50mA ______
463G/CellCom Digital Cellular Communicator Card
Qty _______ x 21mA ______ Qty _______ x 21mA ______
472 FA Wireless Interface Card Qty _______ x 85mA ______ Qty _______ x 85mA ______
481 Expansion Interface Card Qty _______ x 15mA ______ Qty _______ x 15mA ______
1100X Wireless Receiver Qty _______ x 46mA ______ Qty _______ x 46mA ______
1100XH Wireless High Power Receiver Qty _______ x 160mA ______ Qty _______ x 160mA ______
1100XI Wireless In-line Receiver Qty _______ 45mA ______ Qty _______ x 45mA ______
860 Relay Output Module (one relay active)
All four relays active
Qty _______ x 34mA
138mA
______
______
Qty _______ x 34mA
138mA
______
______
865 Style Y or Z Notication Module Qty _______ x 26mA ______ Qty _______ x 85mA ______
866 Style W Notication Module Qty _______ x 45mA ______ Qty _______ x 76mA ______
867 LX-Bus Style W Notication Module Qty _______ x 30mA ______ Qty _______ x 86mA ______
869 Dual Style D Initiating Module Qty _______ x 25mA ______ Qty _______ x 75mA ______
630F Remote Fire Command Center Qty _______ x 63mA ______ Qty _______ x 92mA ______
690 Security Command Keypad Qty _______ x 77mA ______ Qty _______ x 84mA ______
693/793 Easy Entry Keypad
Active Zones (EOL Installed)
Qty _______ x 92mA
1.6mA
______
______
Qty _______
Qty _______
x
x
120mA
*2mA
______
______
790 Security Command Keypad
Active Zones (EOL Installed)
Qty _______ x 77mA
1.6mA
______
______
Qty _______
Qty _______
x
x
84mA
*2mA
______
______
7060/7160 Thinline/7060A Aqualite Keypad Qty _______ x 72mA ______ Qty _______ x 80mA ______
7063/7163 Thinline/7063A Aqualite Keypad Qty _______ x 85mA ______ Qty _______ x 100mA ______
7070/7170 Thinline/7070A Aqualite Keypad
Active Zones (EOL Installed)
Qty _______ x 72mA
1.6mA
______
______
Qty _______
Qty _______
x
x
87mA
*2mA
______
______
7073/7173 Thinline/7073A Aqualite Keypad
Active Zones (EOL Installed)
Qty _______ x 85mA
1.6mA
______
______
Qty _______
Qty _______
x
x
100mA
*2mA
______
______
7760 Clear Touch Keypad Qty _______ x 65mA ______ Qty _______ x 115mA ______
733 Wiegand Interface Module
Active Zones (EOL Installed)
Annunciator (ON)
Qty _______
Qty _______
x
x
30mA
1.6mA
______
______
Qty _______
Qty _______
Qty _______
x
x
x
30mA
*2mA
20mA
______
______
______
734 Wiegand Interface Module
Active Zones (EOL Installed)
Annunciator (ON)
Qty _______
Qty _______
x
x
15mA
1.6mA
______
______
Qty _______
Qty _______
Qty _______
x
x
x
15mA
*2mA
20mA
______
______
______
Copy Sub-Totals to next page Sub-Total Standby
*Based on 10% of active zones in alarm.
______mA Sub-Total Alarm ______mA