Installation guide
Digital Monitoring Products XR500 Series Installation Guide
4
IntRoduCtIon
3.2 Wiring Diagram
The XR500 Series diagram below shows some of the accessory modules you can connect for use in various
applications. A brief description of each module follows in section 3.4.
Heat detectors, pull
stations, or any other
contact devices listed
for Fire Protective
Signaling can be
connected to zones
9 and 10.
Zones 9 and 10 and
Model 715 compatibility
identifier: A
Maximum operating
range: 9.7 VDC to
14.0 VDC.
Class B (Style A).
WARNING: Incorrect
connections may cause
damage to the unit.
Minimum voltage on Auxiliary output
to process Sensor trips is 10.2 VDC.
Auxiliary Power
To tal current combined from
terminals 7, 11, 25, and 27
1.5 Amp Max
10.2 VDC to 14.0 VDC
Listed Resistors
1.0k Ohm - DMP Model 311
3.3k Ohm - DMP Model 309
10K Ohm - DMP Model 308
For Standard Line
Security burglary
applications use
Ademco Model
AB12M bell and bell
housing.
Front and Rear
tamper protection
included with
Model 350A
Attack Resistant
Enclosure.
Bell cutoff time
range is 5 to 99
minutes, non-coded.
Bell
12 VDC
Minimum cutoff time 5 min.
1.5 Amp Max
AC
12345678 10 11 12 13 14 15 16 17 18 199202122232425262728
+B BELL GND SMK GNDREDYEL GRNBLK Z1 Z2 Z3 Z4 Z5 Z6 Z7 Z8 Z9+Z9– Z10+ Z10–AC –B GND GND GNDGND
K6 K7
Output 1Output 2
J3
Phone Line
J10
J22
LX-Bus
Battery
Start
J23
J21
RS-232
Power
LED
J8
PROG
J4
Tamper
J16
Reset
Out1 Out2
Outputs 3-6
J11
3
4
5
6
J2
¼"
J1
Ethernet
R
L
X
Link LED
Activity LED
OVC
XR500 Series
Command Processor™
Panel
1k Ohm1k Ohm1k Ohm
DISARM
ARM
Smoke
Detector
3.3k Ohm 3.3k Ohm 3.3k Ohm 3.3k Ohm
1k Ohm
Form C Relays (J2)
Output Color Code–Model 431 Harness
Output 2 N/OOrange/White
Output 2Com White/Gray
Output 2N/C Violet/White
Output 1N/O Orange
Output 1Com Gray
Output 1N/C Violet
Annunciator Outputs (J11)
Output Color Code
Output 3Red
Output 4Yellow
Output 5Green
Output 6Black
AC Wiring must be in conduit and exit
out the left side of the enclosure.
Wiring on terminals 5 through 22 must
exit right and maintain 1/4" separation
from the AC and battery positive wiring.
Front
Tamper
Rear
Tamper
s
16 to 18 gauge wire
Maximum AC Wire distance
with 16 gauge wire: 70 feet
with 18 gauge wire: 40 feet
RED
BLACK
Cold Water
Pipe Earth
Ground
Bell
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
Zone 6
Zone 7
Zone 8
3.3k
Ohm
Resistor
3.3k
Ohm
Resistor
Zone Expander
Model 715
7mA @ 12 VDC
Models 715-8, 715-16
20mA @ 12 VDC
Use Listed Power Supervision
Relay rated at 12 VDC.
1k Ohm
s
= Supervised Circuit
Zone
9
Zone
10
22 gauge minimum
22 gauge minimum
22 gauge minimum
22 gauge minimum
RED
YELLOW
GREEN
BLACK
1k Ohm1k Ohm1k Ohm
Zone Expander
Model 714
7mA @ 12 VDC
Models 714-8, 714-16
20mA @ 12 VDC
RED
YELLOW
GREEN
BLACK
RED
s
s
s
s s s s s
s
T
he plug-in transformer shall plug
into a 120 VAC 60 Hz outlet not
controlled by a switch and all
16 to
18 gauge wire
shall run through
conduit.
s
s
s
S S S S S S S S
S S S S
1k
Ohm
SS
1k
Ohm
SS
1k
Ohm
SS
1k
Ohm
SS
1k
Ohm
SS
1k
Ohm
SS
1k
Ohm
SS
1k
Ohm
SS
S S
S SS SS S
1k Ohm
Zone Expander
(up to 8 zones)
Model 712-8
19mA @ 12
VDC
S S
Zone
Expander
Model 711
7mA @ 12
VDC
1k
Ohm
s
Keyswitch Arming
can be connected
to any zone.
s
s
s
s s
s s
s
Ground
s
s
s
s
NFPA 72 OPERATING
INSTRUCTIONS
The operating instructions should be
located adjacent to the control unit or
keypad.
HOUSEHOLD FIRE WARNING
Recognized limited energy cable must
be used for connection of all initiating,
indicating, and supplementary devices.
CAUTION: DO NOT USE LOOPED WIRE
UNDER TERMINALS. BREAK WIRE RUN TO
PROVIDE SUPERVISION OF CONNECTIONS.
Zones 9, 10, and all
expanded zones are
suitable for Class B (as
applicable for the
initiating and signaling
line circuits per ANSI/UL
864 Ta ble 48.2 or 48.3).
Installation limits under
local Authority Having
Jurisdiction (AHJ).
Using verification delays
on zones 9 and 10 is
optional. Use the
delays marked on the
smoke detectors.
USE MARKING
Commercial and Residential Fire,
Burglar, Holdup, and Access Protected
Premise Unit
TYPES OF SERVICE
Suitable for Local, Police
Station Connect, Mercantile,
and Proprietary with 350A
Enclosure.
Central Station DACT service
may be provided using 350A
Attack Resistant enclosure.
Suitable for Proprietary, PPU,
other technologies, local.
Suitable for Signaling and
Remote Station PPU DACT
Service.
Suitable for manual fire alarm,
automatic fire alarm, sprinkler
supervisory, or water flow
alarm.
Suitable for Standard or
Encrypted Central Station with
NET or CELL communication.
Suitable for Bank Safe and
Vault Service with 350A
Enclosure.
Suitable for Household Fire
and Household Burglary.
Suitable for Coded and March
Time signaling.
SIA CP-01-2000 minimum
system is XR500, listed local
Bell, and off premise DACT
communication to an SCS-1R
receiver plus listed compatible
keypads as indicated in the
installation guide.
WARNING
THIS UNIT MAY BE PROGRAMMED TO USE AN ALARM VERIFICATION FEATURE THAT
RESULTS IN DELAY OF THE SYSTEM ALARM SIGNAL FROM THE INDICATED CIRCUITS.
THE TOTAL DELAY (CONTROL UNIT PLUS SMOKE DETECTORS) SHALL NOT EXCEED 60
SECONDS. NO OTHER SMOKE DETECTOR SHALL BE CONNECTED TO THESE CIRCUITS
UNLESS APPROVED BY THE LOCAL AUTHORITY HAVING JURISDICTION (AHJ).
Figure 1: XR500 Series Wiring Diagram