Installation guide

Digital Monitoring Products XR500 Series Installation Guide
2
IntRoduCtIon
Panel Features
2.1 Description
TheDMPXR500SeriesCommandProcessor™Panelisaversatile12VDC,combinedaccesscontrol,burglary,andre
communicator panel with battery backup. The XR500 Series provides eight on-board burglary zones and two on-board
12 VDC Class B powered zones. The powered zones have a reset capability to provide for 2-wire smoke detectors,
relays, or other latching devices. The XR500 Series can communicate to one or two DMP SCS-1R Receivers using
digital dialer or network communication, or to non-DMP receivers using the Contact ID format.
2.2 Zone Expansion
Up to 574 additional zones are available on the XR500 Series using DMP LCD keypad remote zone capability and
zone expansion modules. The panel keypad data bus supports up to sixteen supervised device addresses with each
address supporting up to four programmable expansion zones.
Upto500zonesareavailableusingtheonboardLX-Bus,Model461InterfaceAdaptorwith481,462N,462P,463G,
and 472 Interface Cards, and any combination of single, four, eight, or 16-zone expansion modules and single-zone
LX-Bus™ detectors.
Note: Do not use shielded wire for LX-Bus or Keypad Bus circuits.
2.3 Output Expansion
In addition to the two SPDT relays and four programmable open collector outputs on the XR500 Series, you can also
connect up to 25 programmable Model 716 Output Expansion Modules to each LX-Bus. These modules can provide an
additional 500 programmable SPDT relays.
The XR500 Series provides 100 Output Schedules you can use for programming the 716 to perform a variety of
annunciationandcontrolfunctions.Youcanalsoassignthe716outputstoanypanelOutputOptionssuchasFire
Alarm,CommunicationFail,orPhoneTroubleOutputs.Refertothe716InstallationGuide(LT-0183).
TheLX-Bus™alsosupportstheModel717GraphicAnnunciatorModule.Each717modulesupplies20switchedground
outputs that follow the state of their assigned zones.
Note:The717supportsthersteightKeypadBusaddresses.TofollowKeypadBusaddressesninethrough16,install
multiple716modules.Refertothe717InstallationGuide(LT-0235)and716InstallationGuide(LT-0183).
2.4 Central Station Communication
You can program the XR500 Series panel for reporting to DMP SCS-1R Receivers using digital dialer or network
communication. The panel can also communicate to non-DMP receivers using the Contact ID communication
format. The XR500 Series connects at the premises to a standard RJ31X or RJ38X telephone jack. Use the DMP 893A
DualPhoneLineModulewhenconnectingtheXR500Seriespaneltotwoseparatephonelinesinreorburglary
applications.
2.5 Encrypted Communications (XR500N/XR500E only)
An XR500E panel communicates using AES encryption. If you currently have an XR500N panel installed, you may
contact DMP Customer Service with the panel serial number. The serial number(s) should be sent in writing via
e-mailorfax.AseparatefeaturekeyissentforeachpaneltoactivateencryptedcommunicationsusingtheFeature
Upgradeprocess.EncryptedcommunicationcannotbeenabledonastandardXR500panel.Formoreinformationon
theFeatureUpgradeprocessseetheXR500SeriesProgrammingGuide(LT-0679).