Installation Guide XR500 Series Command Processor™ Panel
MODEL XR500, XR500N, XR500E COMMAND PROCESSOR INSTALLATION GUIDE FCC NOTICE This equipment generates and uses radio frequency energy and, if not installed and used properly in strict accordance with the manufacturer’s instructions, may cause interference with radio and television reception.
Table of Contents Product Specifications Summary 1.1 1.2 1.3 1.4 1.5 1.6 1.7 Power Supply..........................................................................1 Communication.......................................................................1 Panel Zones............................................................................1 Keypad Bus.............................................................................1 LX-Bus™...........................................................................
Table of Contents Powered Zones for 2-Wire Smoke Detectors 11.1 11.2 Terminals 25–26 and 27–28...................................................15 Compatible 2-Wire Smoke Detector Chart................................16 Dry Contact Relay Outputs 12.1 12.2 12.3 Description............................................................................17 Contact Rating......................................................................17 Model 431 Output Harness Wiring.......................................
Table of Contents Area Information 22.1 22.2 22.3 22.4 22.5 Ownership............................................................................24 Annunciation.........................................................................24 Trouble Display......................................................................24 Closing Wait..........................................................................24 Local Bell Supervision............................................................
Table of Contents 27.7 Standard or Encrypted Line Security.......................................28 27.8 Wireless Audible Annunciation Option.....................................28 27.9 Model 463G or CellCom, CELL Only, Standard or Encrypted Line Security ...............................................................................28 27.10 Model 463G or CellCom, NET with CELL as Alternate Primary and Dialer Backup, Standard or Encrypted Line Security .................29 27.
Table of Contents 32.5 32.6 32.7 32.8 Detect Wireless Jamming.......................................................34 Wireless External Contact.......................................................34 Wireless Supervision Time......................................................34 Wireless Fire Verification........................................................34 California State Fire Marshal Specifications 33.1 Bell Output Definition.............................................................
Introduction Product Specifications Summary 1.1 Power Supply Transformer Input: Model 327, plug-in — Primary input: 120 VAC, 60 Hz, Secondary output: 16.5 VAC 50 VA Model 322, wire-in — Primary input: 120 VAC, 60 Hz, Secondary output: 16 VAC 56 VA Standby Battery: 12 VDC, 1.0 Amps Max. charging current Models 365, 366, 367, 368, or 369 Replace every 3 to 5 years * Auxiliary: 12 VDC output at 1.5 Amp Max * Bell Output: 12 VDC at 1.
Introduction Panel Features 2.1 Description The DMP XR500 Series Command Processor™ Panel is a versatile 12 VDC, combined access control, burglary, and fire communicator panel with battery backup. The XR500 Series provides eight on-board burglary zones and two on-board 12 VDC Class B powered zones. The powered zones have a reset capability to provide for 2-wire smoke detectors, relays, or other latching devices.
Introduction 2.6 Caution Notes Throughout this guide you will see caution notes containing information you need to know when installing the panel. These cautions are indicated with a yield sign. Whenever you see a caution note, make sure you completely read and understand its information. Failing to follow the caution note can cause damage to the equipment or improper operation of one or more components in the system. See the example shown below.
Introduction 3.2 Wiring Diagram The XR500 Series diagram below shows some of the accessory modules you can connect for use in various applications. A brief description of each module follows in section 3.4. s Suitable for manual fire alarm, automatic fire alarm, sprinkler supervisory, or water flow alarm. SIA CP-01-2000 minimum system is XR500, listed local Bell, and off premise DACT communication to an SCS-1R receiver plus listed compatible keypads as indicated in the installation guide.
Introduction 3.3 Lightning Protection Metal Oxide Varistors and Transient Voltage Suppressors help protect against voltage surges on XR500 Series input and output circuits. Additional surge protection is available by installing the DMP 370 or 370RJ Lightning Suppressors. 3.4 Accessory Devices Interface Adaptor and Interface Cards 461 Interface Adaptor Card Allows you to connect two or more expansion interface cards to the XR500 Series panel.
Introduction 3.4 Accessory Devices (continued) DMP Two-Way Wireless Devices (continued) * 1131 Recessed Contact Provides a recessed contact option for door or window applications. * 1139 Bill Trap Provides a silent alarm option for retail and banking cash drawers. 1142BC Two-button Hold-up Belt Clip Transmitter Provides two-button hold-up operation with a belt clip. 1142 Two-button Hold-up Transmitter Provides permanently mounted under-the-counter two-button hold-up operation.
Installation Installation 4.1 Mounting the Enclosure The metal enclosure for the XR500 Series must be mounted in a secure, dry place to protect the panel from damage due to tampering or the elements. It is not necessary to remove the XR500 Series PCB when installing the enclosure. Figure 2 shows the mounting hole locations for the Model 350/350A Enclosures. Figure 3 shows the Model 341 Small Enclosure. Figure 4 shows the Model 352X panel cabinet and 352S shelf cabinet for multiple batteries.
Installation 56 VA Transformer Mounting Plate J3 Phone Line J4 Tamper J1 Ethernet Link LED Activity LED Power LED R L X J23 RS232 5 4 3 2 XR500 Series 1 G 9 8 7 6 J22 LX-Bus RED J10 Output 1 OVC AC +B 1 2 3 Out2 –B BELL GND RED YEL GRN BLK SMK GND Z1 GND Z2 4 5 6 7 8 9 10 11 12 13 14 K7 Outputs 3-6 AC J6 Expansion Slot Output 2 Out1 RED K6 J8 Z3 GND Z4 Z5 GND Z6 15 16 17 18 19 J16 Reset 20 21 Z7 GND Z8 Z9+ Z9– Z10+Z10– 22 23 24 25 26 27 28 Mounting for
Installation 4.3 Connecting LX-Bus and Keypad Bus Devices Several factors determine the DMP LX-Bus™ and keypad bus performance characteristics: the wire length and gauge used, the number of devices connected, and the voltage at each device. When planning an LX-Bus™ and keypad bus installation, keep in mind the following information: 1. DMP recommends using 18 or 22-gauge unshielded wire for all keypad and LX-Bus circuits. Do not use twisted pair or shielded wire for LX-Bus and keypad bus data circuits. 2.
Installation Secondary Power Supply 6.1 Battery Terminals 3 and 4 Connect the black battery lead to the negative battery terminal. The negative terminal connects to the enclosure ground internally through the XR500 Series circuit board. Connect the red battery lead to the battery positive terminal. Observe polarity when connecting the battery. You can add a second battery in parallel using the DMP Model 318 Dual Battery Harness.
Installation 6.8 XR500 Series Power Requirements During AC power failure, the XR500 Series panel and all connected auxiliary devices draw their power from the battery. All devices must be taken into consideration when calculating the battery standby capacity. The following table lists the XR500 Series panel power requirements.
Installation Standby Battery Power Calculations Standby Current Alarm Current 736P POPIT Interface Module Radionics Popex, POPITs, OctoPOPITs Qty _______ Qty _______ x 25mA ______ x ___mA ______ Qty _______ Qty _______ x x 25mA ______ ___mA ______ 738A Ademco Wireless Interface Module Qty _______ x 75mA ______ Qty _______ x 75mA ______ 710 Bus Splitter/Repeater Module Qty _______ x 32mA ______ Qty _______ x 32mA ______ 710F Fire Bus Splitter/Repeater Module Qty _______ x 40mA _____
Installation 6.9 Standby Battery Selection To choose the type and number of batteries needed for 24, 60, or 72 hours of standby power based on the Amp Hours Required calculation from section 6.8 XR500 Series Power Requirements, perform the following: 1. Select the desired standby hours required from the table below: 24, 60, or 72 hours 2. Select the desired battery size: Model 368 (12 VDC 4.5 Ah), Model 369 (12 VDC 7 Ah), Model 367 (12 VDC 7.7 Ah), Model 365 (12 VDC 9 Ah), Model 366 (12 VDC 18 Ah). 3.
Installation Bell Output 7.1 Terminals 5 and 6 Terminal 5 supplies positive 12 VDC to power alarm bells or horns. This output can be steady, pulsed, or temporal depending upon the Bell Action specified in Bell Options. Terminal 6 is the ground reference for the bell circuit. This supervised output detects 1k Ohms or less as normal. The indicating appliance can supply this resistance.
Installation Protection Zones 10.1 Terminals 13–24 Zones 1 to 8 (terminals 13 to 24) on the XR500 Series panel are all grounded burglary zones. For programming purposes, the zone numbers are 1 through 8. Listed below are terminal 13 to 24 connection functions.
Installation 11.2 Compatible 2-Wire Smoke Detector Chart Manufacturer Model Detector ID Base Detection Systems DS230, DS230F B/A MB2W, MB2WL A 8.5-33 10 Detection Systems DS250, DS250TH B MB2W, MB2WL A 8.5-33 10/12 Detection Systems DS250HD B MB2W, MB2WL A 8.5-33 10 B/A MB2W, MB2WL A 8.5-33 17 8.
Installation Dry Contact Relay Outputs 12.1 Description The XR500 Series panel provides two programmable auxiliary SPDT relays when equipped with two DMP Model 305 relays in sockets K6 (Output 1) and K7 (Output 2) and a Model 431 Output Harness on the J2 6-pin Header.
Installation J23 6-Pin Header 14.1 Description The XR500 Series Command Processor™ panel supports RS-232, LX-Bus, and DMP Wireless operation. Only one operation can function at a time. Install a jumper on one pair of J23 headers to indicate how the panel is programmed to operate. Refer to the table below when installing a jumper on J23. When a jumper is installed or moved on the 6-pin header, briefly reset the panel using the J16 jumper to activate the selected operation.
Installation 15.3 LX-Bus Interface Cards You can add one Interface Card (Model 481, 462N, 462P, 463G, or 472) to the XR500 Series using J6 Interface Card Connector located on the board right edge. To add more than one Interface Card install a 461 Interface Adaptor Card using J6 Interface Card Connector on the board right edge. The 461 Adaptor Card allows up to five Interface Cards to be installed. Refer to the 461 Installation Sheet (LT-0736). Each Interface card provides up to 100 LX-Bus Zones.
Installation 16.3 Direct iCOM Connection to J21 Use DMP Model 397 cable with a DB-9 female connector on one end and an RJ connector on the other end. Mount the iCOM in the panel enclosure. Refer to the iCOM Installation Guide (LT-0587). Plug the 397 cable DB-9 male connector end onto the XR500 Series panel J21 RS-232 connector. Plug the RJ connector into the iCOM J1 Network connector. Program the XR500 Series panel as needed. 16.
Installation The wires on the RJ31 that feed pins 4 and 5 should be the ONLY wires on the D-marc. All other house phone wiring should be tied to pins 1 and 8 coming back from the RJ31. Dial tone must come into RJ31X on pins 4 and 5 and go back to house phones from pins 1 and 8. Follow these steps to determine if panel is seizing the line: 1. Unplug phone cord from RJ31X 2. Place butt-set on pins 4 and 5 3. Listen for dial tone. With dial tone present, lift either wire from pins 1 or 8 4.
Installation Reset and Tamper Headers 19.1 J16 Reset Header The reset header is located just above the terminal strip on the right side of the circuit board and is used to reset the XR500 Series microprocessor. To reset the panel when first installing the system, install the reset jumper before applying power to the panel. After connecting the AC and battery, remove the reset jumper.
Compliance Listed Compliance Specifications 20.1 Introduction For applications that must conform to a local authorities installation standard or a National Recognized Testing Laboratory certificated system, please see the following sections. Universal Burglary Specifications 21.1 Introduction The programming and installation specifications contained in this section must be completed when installing the XR500 Series panel in accordance with any of the burglary standards.
Compliance Area Information 22.1 Ownership The control unit system shall be under one ownership. 22.2 Annunciation The System shall be installed so that when arming any area from any keypad, the local bell shall annunciate. 22.3 Trouble Display The Status List programming shall be set to annunciate all trouble messages at all keypads. 22.4 Closing Wait The Closing Wait option must be programmed YES. 22.
Compliance 24.4 Exit Delay The maximum exit delay used must not be more than 60 seconds. 24.5 Proprietary Dialer The Model XR500 Series provides proprietary service when configured as a digital dialer. 24.6 DACT Central Station DACT Central Station service can be provided under by adding an Ademco AB12M bell and bell housing and placing the Model XR500 Series panel into Model 350A or 350H Attack Resistant Housing. 24.7 Bell Cutoff The Bell Cutoff time cannot be less than 15 minutes. 24.
Compliance 24.11 Model 463G or CellCom, NET with CELL as Alternate Primary and Dialer Backup, Standard or Encrypted Line Security Standard or Encrypted Line Security is provided using NET communication with CELL as an alternate primary and with digital dialer as a backup. XR500 network communication is used as primary with a 6 minute check-in when armed, and a random check-in over a 60 minute period when disarmed. CELL is the backup path and set to daily test.
Compliance Holdup Alarm Units ANSI/UL 636 25.1 ANSI/UL 1610 Required The programming and installation specifications contained in this section must be completed in addition to ANSI/UL 1610 Specifications when installing a Model 1142 with a Model XR500 Series panel. 25.2 1100X Wireless Receiver The Model 1100X Wireless Receiver in conjunction with the Model 1142 Holdup Alarm Transmitter must be installed in the system. 25.
Compliance 27.4 Bell A local audible signal appliance must be used such as Ademco AB12M bell and bell housing. The alarm housing for a mercantile alarm system without a remote alarm transmission connection shall be mounted on the outside of the building, visible from a public street or highway. It shall be accessible for examination and repair.
Compliance 27.10 Model 463G or CellCom, NET with CELL as Alternate Primary and Dialer Backup, Standard or Encrypted Line Security Standard or Encrypted Line Security is provided using NET communication with CELL as an alternate primary and with digital dialer as a backup. XR500 network communication is used as primary with a 6 minute check-in when armed, and a random check-in over a 60 minute period when disarmed. CELL is the backup path and set to daily test.
Compliance 28.4 Mercantile Safe and Vault When the DMP Model 350A or 350H Attack housing is used, the XR500 Series provides operation as a mercantile safe and vault alarm. Bell Supervision and wiring must be in accordance with ANSI/UL 681. When the XR500 Series is mounted outside the safe or vault, tamper protection and the Sentrol Model 5402 or Potter EVD listed vibration detectors should be used. 28.5 Bell A local audible signal appliance must be used such as Ademco AB12M bell and bell housing.
Compliance Universal Fire Alarm Specifications 30.1 Introduction The programming and installation specifications contained in this section must be completed when installing the Model XR500 Series in accordance with any of the ANSI/UL or NFPA fire standards. Additional specifications may be required by a particular standard. See the XR500 Series Programming Guide (LT-0679). 30.2 Wiring All wiring must be in accordance with NEC, ANSI/NFPA 70. 30.
Compliance Control Units for Fire-Protective Signaling Systems ANSI/UL 864, NFPA 72 31.1 Power Supply 31.2 Zone Restoral Reports For listed installations, the total current combined from Auxiliary and Bell Power cannot exceed: 1.2 Amps with a 56 VA transformer; .5 Amp Max for Auxiliary Power and .7 Amp Max for Bell For listed installations, the 50 VA Plug-in transformer cannot be used. The total combined current from Terminals 7, 11, 25, and 27 cannot exceed 1.2 Amps.
Compliance 31.6 Local Protective Signaling Systems The DMP Model 865, 866, or 867 Notification Circuit Module must be used on the bell circuit for detection of shorts and grounds. Any burglary or other off premises communication must be done with the Model 893A Dual Phone Line Module. For local commercial fire installations, the 893A is required. 31.7 Remote Station Protective Signaling Systems You must provide 60 hours of standby battery. See section 6.
Compliance 31.9 Combination Systems For combination fire and burglary systems, powered burglary devices (PIR, Glassbreak, etc.) must be powered from a separate listed power supply (DMP Model 505-12). This requirement is not needed for non-powered burglary devices (door contacts, etc.) which only connect to the zone input of zone expanders or keypads. Refer to Powered Burglary Devices later in this document.
Compliance 32.4 Bell Cutoff The Bell Cutoff time cannot be less than five minutes. 32.5 Detect Wireless Jamming The Detect Wireless Jamming option must be programmed YES. 32.6 Wireless External Contact When used, the External Contact of 1101 or 1102 must be programmed Normally Closed. 32.7 Wireless Supervision Time The Zone Information Supervision Time must be 240 minutes. 32.
Compliance False Alarm Reduction Programmable Options * 35.1 Shipping Defaults and Recommended Programming for ANSI/SIA CP-01-2000 SIA CP-01 FEATURE PARAGRAPH # AND DESCRIPTION DMP XR500 PROGRAMMING GUIDE LT‑0679 SECTION # REQUIREMENT RANGE 4.2.2.1 Exit Time 15.2 Exit Delay Required 45 sec. - 250 sec. (Programmable) 4.2.2.2 Progress Annunciation 15.2 Exit Delay Allowed 4.2.2.3 Exit Time Restart 15.2 Exit Delay Required Option 4.2.2.
Compliance False Alarm Reduction Programmable Options (continued) 35.2 Call Waiting (ANSI/SIA CP-01-2000) The Call Waiting default setting is disabled. To cancel the Call Waiting feature, program * (star) 7 0 P (pause), the standard telephone code prefix that cancels call waiting, into the telephone number string. Cancel Call Waiting for telephone lines that have Call Waiting operational on the telephone line. See the XR500 Series Programming Guide (LT‑0679).
Wiring Diagrams Wiring Diagrams 37.1 866 with NAC Extender To panel zone To panel alarm output To panel terminal 7 To panel zone To panel terminal 10 Normal/Silence Switch DMP Model 866 45mA @ 12 VDC The 866 Notification Appliance Circuit Module in alarm draws up to 31mA through its Terminal 3 Alarm Input and 45mA from its Terminal 1 Aux Power Input.
Wiring Diagrams 37.
Wiring Diagrams 37.
Wiring Diagrams 37.
Wiring Diagrams 37.
Wiring Diagrams 37.
Wiring Diagrams 37.
Wiring Diagrams 37.
Wiring Diagrams 37.
Wiring Diagrams 37.
Wiring Diagrams 37.
Wiring Diagrams 37.
Wiring Diagrams 37.13 Panel Slave Communicator for FACP using Outputs J4 Tamper J3 Phone Line XR500 Series Command Processor™ Panel Communication Fail Output 1 must be programmed as a Comm Fail output in Output Options.
Wiring Diagrams 37.
Wiring Diagrams 37.15 Derived Channel Installation Using Bosch D8122 XR500 Series Command Processor™ Panel J4 Tamper J3 Phone Line Form C Dry Contact Relays (J2) Output Color Code–Model 431 Harness Output 2 N/O Orange/White Output 2 Com White/Gray Output 2 N/C Violet/White Output 1 N/O Orange Output 1 Com Gray Output 1 N/C Violet J1 J21 Output Header J2 for K6 and K7 Dry Contact Relays. All outputs must be connected to devices located within the same room as the panel.
XR500 Series Installation Guide Green LED Red LED Silence BLO BLI Test Common + 12 VDC Rothenbuhler 5110 High Security Bell K3 R L X J23 J10 J22 RS-232 J21 J1 J4 Tamper K6 J2 1 3 4 Output 1 N/C Output 2 N/C 2 5 6 S 7 9 S 10 12 13 14 15 16 Output 1 Common 11 10K EOL DMP Model 308 Output 2 Common 8 J11 18 19 10K EOL DMP Model 308 17 20 J16 Reset 24 25 26 27 28 S = Supervised Circuit 23 Model 431 Output Harness 21 22 Z3 GND Z4 Z5 GND Z6 K7 J6 Interface Card Ex
Wiring Diagrams 37.17 LX-Bus™ Module Connection LX-Bus Expansion Interface Card DMP Models 481, 462N, 462P, 463G, or 472 Each LX-Bus Module must have its own independent address ranging from 00 to 99. A Supervisory zone must be programmed into the XR500 Series to properly supervise each module.
Wiring Diagrams 37.18 Model 860 Relay Module Connection XR500 Series Command Processor™ Panel J4 Tamper J3 J2 Output Header All outputs must be located within the same room as the control panel.
Revisions Revisions to This Document This section explains the changes that were made to this document during this revision. This section lists the version, section number with heading, and a quick summary of the change. Version 1.09 1.08 Section Number and Heading Summary of Changes 31.8 Fire Protective Signaling Systems Updated to reflect Cell/Net Primary Fire options 31.8 Fire Protective Signaling Systems Updated to reflect 463G Commercial Fire 37.
800-641-4282 INTRUSION • FIRE • ACCESS • NETWORKS www.dmp.