Installing the DL600E Unit 2-5
Installing the DL600E Unit Using DC Power
Allow two to three feet of clearance around the DL600E unit to give you
access during the installation.
Warning!
Take care when connecting to DC power. If you connect the
DL600E unit improperly, you may damage it.
To Connect the DL600E Unit to DC Power
Use only a DC cable that is UL recognized 14 AWG, 3 conductors, copper
strand wire, electrical power and control cable, type
TC. An example is:
600 V, 90 degree C. Alpha Wire Company No. 45443.
Referring to Figure
2-1, use the following procedure:
1 Install the DL600E unit in the 19Ó rack.
2 Ground the DL600E unit to earth ground using a grounding
cable connected to the ground stud on the back panel. The
grounding cable is described in Appendix
A.
3 Make sure the DC power source is off.
4 Before connecting the DL600E unit to the centralized DC
power source, strip
2 inches (5.08 cm) of jacket material from
the
DC cable and 1/2 inch (1.25 cm) of insulation from the
end of each wire.
5 Connect the -48V wire to the negative (-) terminal of the
DL600E unit using a small ßat screw driver to fasten the wire.
6 Connect the ground wire to the positive (+) terminal in the
same way.
D The unit is designed to operate with negative voltage.
Therefore, the
positive (+) terminal is connected to ground.
7 Connect a third wire to the ground stud near the terminal
block and to a good ground using a 1/4 inch (.635 cm)
wrench
and fastening torque of
5 lbs/ft. (.6 kg/ft.).