Instruction manual
MXS-EVO - MANUAL
-------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
MXS-EVO – Manual – Rev 1.7 - 15 -
It was also implemented part of the standard 1344-1995. The offset compared to the UTC time can be set using the
Timezone of the apparatus. Changes of DST or leap second are not currently notified (always returned as 0).
The device can output both an IRIG-B DCLS and IRIG-B AM signals.
It can also recognize an IRIG-B DCLS signal via a BNC or optical connector.
When the BNC connector is used it inhibits the external timing input.
Date and time
The device disciplines its internal clock from the selected reference (GPS, PTP, IRIG-B, NTP) and distributes it with
the following rules:
• NTP (UTC timebase as per standard)
• PTP (TAI timebase as per standard)