Technical data

Testing 5
1.2 Running a Self-Test
Self-test allows you to test every device again after power-up tests are
complete. Devices can be tested individually (except for drives), a few at a
time, or all of them sequentially just like power-up tests.
To individually test a device (drives are tested all together on their
particular bus), enter the word (TEST) or just the letter (T), followed by
a space and the test number of the device you want tested. Table 1–1
lists the devices and the test numbers that test the devices. Example 1–4
shows an example of running a self-test on an SCSI bus. All devices
connected to the SCSI bus are tested and the results are listed in the
configuration table (TEST 50).
>>> TEST 6
6...
>>>
NOTE: Enter TEST 50 to see the results
Example 1–4 Running a Self-Test on an SCSI Bus
1.2.1 Self-Test with Loopback Connectors
A customer mode self-test (that is, without any serial line loopbacks) does
not test the drivers on the serial lines (DZ). To test the DZ drivers, run a
self-test on the serial lines in field service mode by installing loopbacks
on the two MMJ connectors, then run TEST C. Display the configuration
table to see the results.
If only one MMJ loopback is available, install it in the communications
port and run the tests. An error code of 0000.0200 for the DZ indicates
that the printer port does not have the loopback installed but the
communications port tested successfully.
NOTE
The ThinWire Ethernet port or the standard Ethernet port
(depending on which port the customer is using) on the back
of the system box must be terminated properly when running
diagnostics on the Ethernet circuits (TEST 1). Otherwise an error
code of 0000.7001 or greater is listed in the configuration table.