User`s guide
StorageWorks RAID Array 200 Controller Installation and Standalone Configuration Utility
9–6 EK–SWRA2–IG. C01
9.2.2 Updating the Firmware on an AXP System
To update your firmware on an AXP-based system, follow these steps:
1. Consult your AXP system documentation to invoke the boot menu shown
below.
2. Insert the latest standalone configuration utility for AXP Systems floppy
diskette into your floppy drive.
3. Use the up and down arrow keys to highlight the Run a program option, and
press the Enter key to select it. The utility displays a prompt.
4. To run the utilities from the A: drive, do the following:
For a single RAID controller, type this command:
Program to Run: A:\SWXCRFW xxxx.xxx
where xxxx.xxx is the firmware filename (typically, SWXCRFWA, for
EISA; SWXCRFWP, for PCI) and version of the firmware that you want to
load; SWXCRFWA.215 (EISA), SWXCRFWP.219 (PCI), for example.
NOTE
If you have both EISA and PCI controllers to
update, perform the next step for the EISA
controller(s) first.
For multiple controllers, either EISA or PCI, type:
A:\SWXCRFW –v xxx
where xxx is the version of the firmware, 215 for EISA or 219 for PCI.
ARC Multiboot DEC Version 2.07
Copyright © 1993 Microsoft Corporation
Copyright © 1993 Digital Equipment Corporation
Boot Menu
Boot Windows NT
Boot an alternate operating system
Run a program
Supplementary menu ...
Use the arrow keys to select, then press Enter.