Technical data

Output speed: 9600 baud
The summary sheet and the terminal settings should be the same.
If your printer interface runs at a different speed, make sure you set the same
configuration switch settings and device characteristics.
If the printer is connected directly to the host, check the baud rate setting in
the printer startup command file. If you did not enter a baud rate in parameter
p6 of the execution queue definition, the startup procedure sets the printer
speed at 9600 baud. Refer to the SET TERMINAL command in the OpenVMS
DCL Dictionary for information on changing the system’s interpretation of the
device characteristics.
If your printer is connected by a LAT device to a local area Ethernet, see
Section 11.1.3.
If the settings agree and the job still does not print, go to step 3.
Step 3: Check communications software
Test the operation of the communications equipment by attempting to send
data directly to the device. To perform this procedure, make sure the queue is
paused (see Section 5.7).
The device must not be spooled to accomplish this procedure. If the device is
spooled, enter the following command:
$ SET DEVICE LTAnnnn:/NOSPOOL
To test the communications setup, issue the SET HOST/DTE command to the
printer. Use the commands in the following examples:
$ SET HOST/DTE LTA9092:
Connection established, type ^\ to exit
Ctrl/T
%%[ status: idle ]%%
After you press Ctrl/T, you should receive a message in the form of
%%[Status: description]%%. If you receive this message, the connection to the
printer is established and working.
If no message of this type is displayed, enter the commands in the following
example:
^\
$ COPY TT: LTA9092:
showpage
Ctrl/Z
$
Troubleshooting Procedures 11–3