5.4 Checking Conversion Result
5.4.1 Conversion log list
(Continued to next page)
Log
code
Message
Conversion
result
Corrective action
3000 Display data too large. Error
Before conversion, set the object in a proper position using screen editor
software.
3001 The objects not supported. Error After the conversion, create a substitute for the error object with GT
Designer2. Manually create a substitute object.
3002 Figure (Figure no.) conversion
completed.
OK
---
3003 Figure (Figure no.) conversion failed. Error Correct the error occurred before this error.
3004 Tag (Tag name) conversion
completed.
OK
---
3005 Tag (Tag name) conversion failed. Error Correct the error occurred before this error.
3006 Parts (Parts name) conversion
completed.
OK
---
3007 Parts (Parts name) conversion failed. Error Correct the error occurred before this error.
4000 Data call from CF card not
supported.
Error Before conversion, change the object setting to other than "CF card" using
screen editor software.
4001 Unable to convert indirect devices. Error Before conversion, change the warning settings of the object to "direct
specification" using the screen editor software.
4002 Indirect color specification is not
supported.
Warning Before conversion, change the color settings of the object to "direct
specification" using the screen editor software.
4003 Signed MSB not supported. Error Before conversion, change the input code of the object to other than MSB
code using the screen editor software.
4004 Unable to convert color blocks. Error Before conversion, cancel the color block setting of the object using the
screen editor software.
4005 Unable to convert slanted tags. Error Before conversion, set the tag angle to 0 degrees using the screen editor
software.
4006 Data compressed. Error Before conversion, decompress the data using the screen editor software.
4007 Maximum points limit exceeded. Warning Before conversion, reduce the number of figures' points to 1,000 or less
using the screen editor software.
4008 Data error. Error After the conversion, create a substitute for the error object with GT
Designer2.
4009 Conversion of text screen number
failed.
Warning Change the total number of lines on the text screen to 12,000 or less.
4010 Maximum line spacing limit
exceeded.
Warning After the conversion, change the position of the character string with GT
Designer2.
4011 Unable to convert arrow attributes. Warning After the conversion, draw an arrow using lines with GT Designer2.
4012 Unable to convert BMP image in
parts.
Error After the conversion, register the BMP image as a part with GT Designer2.
5000 Syntax error. Error Before conversion, correct the script syntax error with the screen editor
software.
5001 Unable to convert script trigger. Error After the conversion, manually set the trigger with GT Designer2.
5002 Unable to convert script. Error Before conversion, remove the command that is not supported by GT
Converter2 using the screen editor software.
5003 Unsupported special relay is
converted to GD device.
Warning After the conversion, set the GD device to an appropriate device with GT
Designer2.