Specifications
Core Software Operation
ADDvantage-32 PLUS ● AC to DC Power Converter
3-19
3.7 RUN, THREAD, AND JOG INPUTS
Y*** Parameters
Y***:RUN INPUT
Y***:JOG INPUT
Y***:THRD INPUT
These three parameters enable the control loops of the ADDvantage-32 PLUS. Each
parameter can be configured to a value in the digital data table which enables its
particular function. These three parameters are interlocked. Therefore, only one can be
enabled at a time. Consult the Logic Sequence description provided in this section for
specific interlock information.
Example: Assume the following inputs are being used to run, jog, or thread the section:
Digital Input 1 = Run Section
Digital Input 2 = Jog Section
Digital Input 3 = Thread Section
1. The values for the three digital inputs in the Digital Data Table are: D***:USER
1 for digital input 1, D***:USER 2 for digital input 2, and D***:USER 3 for
digital input 3.
2. Configure the parameters as follows:
Y***:RUN INPUT = D***:USER 1
Y***:JOG INPUT = D***:USER 2
Y***:THRD INPUT = D***:USER 3
3.8 ANALOG INPUTS
X*** Parameters A*** Parameters
X***:INPT #1 CAL A***:ANALOG IN 1
X***:INPT 1 ZERO A***:ANALOG IN 2
X***:INPT #1 TC A***:ANALOG IN 3
X***:INPT #2 CAL A***:ANALOG IN 4
X***:INPT #2 ZERO A***:ANALOG IN 5
X***:INPT #2 TC A***:ANALOG IN 6
X***:INPT #3 CAL
X***:INPT #3 ZERO
X***:INPUT #3 TC
X***:INPUT #4 CAL
X***:INPUT #4 ZERO