Specifications
Preparation for Use
ADDvantage-32 PLUS ● AC to DC Power Converter
6-6
TABLE 6-2A. WIRE TERMINATION KIT GUIDE FOR PART NUMBERS
WITH “N” IN THE NINTH POSITION
(Example: DC0056-4DN2-C)
↑
AC INPUT (L1,L2,L3)
MOTOR ARMATURE
OUTPUT
(A1,A2,DB)
CHASSIS GROUND
MOTOR
FIELD***
DRIVE
PART NO.
WIRE
TERMINA-
TION
KIT
PART NO.
Stud
Size
Recommended
Wire Size
Bolt
Size
Recommended
Wire Size
Bolt
Size
Recommended
Wire Size
Recommended
Wire Size
DC0010 A21560 1/4" 10 AWG *** 10 AWG 1/4-20 10 AWG 12 AWG
DC0030 A21561 1/4" 8 AWG *** 6 AWG 1/4-20 10 AWG 12 AWG
DC0056 A21562 1/4" 4 AWG * 2 AWG 1/4-20 10 AWG 12 AWG
DC0110 A21563 1/4" 1/0 AWG 1/4"
STUD
2/0 AWG 1/4-20 6 AWG 12 AWG
DC0180 A21564 3/8" 4/0 AWG 3/8"
STUD
2 × 1/0 AWG
**
3/8-16 6 AWG 12 AWG
DC0280 A21565 3/8" 2 × 2/0 AWG
**
3/8"
STUD
2 × 3/0 AWG
**
3/8-16 4 AWG 12 AWG
DC0360 A21566 3/8" 2 × 3/0 AWG
**
3/8"
STUD
2 × 250 MCM
**
3/8-16 2 AWG 12 AWG
DC0510 A21567 3/8" 2 × 300 MCM
**
1/2"
STUD
2 × 400 MCM
**
3/8-16 1/0 AWG 12 AWG
* Wire termination is made to lug attached to the drive contactor (K1).
** Indicates two wires of the same size in parallel.
*** No lugs are required for these connections. Strip insulation 0.31" from end of wire. Make connections to TB1 on top
of the drive.
NOTE
Refer to rating nameplate for voltage and current ratings.
Recommended wire sizes are based on NEC TABLES 310-16 and
310-17 for copper wire. Conductor sizes are based on 60ºC table
for currents below 100A and 75ºC table for currents above 100A.
Derating factor of 0.82 for 60 degree wire used in 36-40 degree
ambient, 0.88 for 75 degree wire used in 36-40 degree ambient.
See N.E.C. Section 250-95 for grounding conductor sizing. Sizes
may also be adjusted to meet certain lug compatibility/
requirements. These sizes may differ from the drive internal and
panel wires. Always consult local building codes to determine the
requirements of your application.
The 3-phase AC input power connections (L1, L2, L3) are made to studs on top of the
drive base assembly. (Refer to Table 6-2 or 6-2a.) These connections require terminal
lugs for proper connection.