Specifications
Preparation for Use
ADDvantage-32 PLUS ● AC to DC Power Converter
6-5
TABLE 6-2. WIRE TERMINATION KIT GUIDE FOR PART NUMBERS
WITHOUT “N” IN THE NINTH POSITION
(Example: DC0056-4D02-C)
↑
AC INPUT (L1,L2,L3)
MOTOR ARMATURE
OUTPUT
(A1,A2,DB)
CHASSIS GROUND
MOTOR
FIELD***
DRIVE
PART NO.
WIRE
TERMINA-
TION
KIT
PART NO.
Stud
Size
Recommended
Wire Size
Bolt
Size
Recommended
Wire Size
Bolt
Size
Recommended
Wire Size
Recommended
Wire Size
DC0010 A20741 1/4" 10 AWG * 10 AWG 1/4-20 10 AWG 12 AWG
DC0030 A20742 1/4" 10 AWG * 8 AWG 1/4-20 10 AWG 12 AWG
DC0056 A20743 1/4" 6 AWG * 4 AWG 1/4-20 10 AWG 12 AWG
DC0110 A20744 1/4" 1/0 AWG * 2/0 AWG 1/4-20 6 AWG 12 AWG
DC0180 A20745 3/8" 3/0 AWG 1/4-20 2 × 1/0 AWG
**
3/8-16 6 AWG 12 AWG
DC0280 A20746 3/8" 2 × 1/0 AWG
**
3/8-16 500 MCM 3/8-16 4 AWG 12 AWG
DC0360 A20747 3/8" 2 × 3/0 AWG
**
3/8-16 2 × 4/0 AWG
**
3/8-16 2 AWG 12 AWG
DC0510 A20748 3/8" 2 × 300 MCM
**
1/2"
STUD
2 × 400 MCM
**
3/8-16 1/0 AWG 12 AWG
* Wire termination is made to lug attached to the drive contactor (K1).
** Indicates two wires of the same size in parallel.
*** No lugs are required for these connections. Strip insulation 0.31" from end of wire. Make connections to TB1 on top
of the drive.