Specifications

Control Block Description
ADDvantage-32 PLUS
4-87
4.59 RECIPE
1. Inputs
RECA: Analog
RECB: Analog
RECC: Analog
ENA: Bit
ENB: Bit
ENC: Bit
EN: Bit
2. Outputs
OUT: Analog
FLT: Bit
3. Implementation
RECA, RECB, RECC points to the first address of 10 consecutive calibration locations.
OUT points to the first address of 10 consecutive analog locations.
On powerup, the OUT locations (10 values) are set to the RECA values.
When the EN bit is high, the block will select which block of 10 values to output based
on the ENA, ENB, and ENC bits.
ENA transfers RECA data.
ENB transfers RECB data.
ENC transfers RECC data.
When EN is low, no transitions occur.
ENA has the highest priority and is also used when no enable is present.
ENB is the second highest priority.
On powerup, FLT output bit is low.
Whenever EN is enabled, the FLT output is checked. FLT will go high if no bits are selected or
if more than one is selected.