Operating instructions
4 - 20
MAN0443.P65 Issue 13 Aug 04 5701 Control System
05701-M-5001 A02279
CHAPTER 4 - INSTALLATION INSTRUCTIONS
Sensor Line Resistance
Maximum Cable Length (m)
Device or Sensor Type
Conductor Cross Sectional Area (mm˝)
0.50 0.75 1.00 1.50 2.50
704/705 500 750 1000 1500 2500
7
80 (at 200mA bridge current)
500 750 1000 1500 2500
811 5600 8400 11200 16800 28000
910 (Single pair at 200mA) 480 720 960 1400 2400
910 (2 pair at 200mA) 230 340 460 690 1100
911 5600 8400 11200 16800 28000
Apex - Toxic 180 270 360 540 900
Apex - Combustible/Thick Film 130 195 260 390 650
Digi-Cat Combustible 400 600 800 1200 2000
Digi-Chem 1000 1500 2000 3000 5000
Digi-Ana 1000 1500 2000 3000 5000
Digi-Optima 180 270 360 540 900
Life Line 3200 4800 6400 9600 16000
Opus/LLII - Toxic 300 450 600 900 1500
Opus/LLII - Combustible 250 375 500 750 1250
Searchline
(minimum dc supply 21V) 60 90 120 180 300
Searchpoint 500 32 48 64 96 160
Searchpoint OPTIMA
(minimum dc supply 19V) 180 270 360 540 900
Series 2000 Combustible 450 670 900 1300 2200
Series 2000 Toxic 1600 2400 3200 4800 8000
Searchline Excel Receiver
(minimum dc supply 21V) 90 135 179 271 449
Searchline Excel
Transmitter (S/R)
(minimum dc supply 21V) 141 211 282 425 704
Searchline Excel
Transmitter (L/R)
(minimum dc supply 21V) 94 141 188 283 998
Searchline Excel Cross Duct
Transceiver assembly
(minimum dc supply 21V) 55 82 109 165 274
Searchpoint Optima Plus 159 237 315 476 787
SensePoint Flam. LEL/ppm 500 750 1000 1500 2500
SensePoint Toxic 3200 4800 6400 9600 16000
SignalPoint Flamable 500 750 1000 1500 2500
Signal Point Toxic 2000 3000 4000 6000 10000