Operating instructions

8 - 5
MAN0443.P65 Issue 13 Aug 04 5701 Control System
05701-M-5001 A02279
CHAPTER 8 - SPECIFICATION
5.2 Single Channel Control Card
Four-Part Liquid Display:
Analogue Display: 25 segment.
Digital Display: Four character.
Message Display: Four character.
Icon Section: Power On/Card Select.
LEDs: A1, A2, A3 gas alarms.
Fault and Inhibit.
Push-Button: Alarm Reset/Card Select.
Alarm Setting Point
Resolution: In 1% fsd steps.
Display/Alarm Point:
Linearity: ±1% fsd.
Repeatability: ±1% fsd.
Remote Facilities: Inhibit/Alarm Reset.
Remote Inhibit / Reset Inputs
Active For Inputs: More than 2V.
Maximum Input Voltage: 32V.
Maximum Input Current: 5mA.
Power Consumption:
Catalytic: 3.75W (typical).
(Includes Catalytic Sensor).
4 - 20mA: 3.25W (typical).
DC Supply: 18V to 32V dc.
Electronic Drift: Less than ±2% / 6 months.
Dimensions: Height: 112mm.
Width: 25mm.
Depth: 170mm.
Weight: 165g.