CHAPTER 6 - OPERATING INSTRUCTIONS
21/07/97 11:06 ** Card info **
Slot : 01
Card type : 5701
Sensor type : 4-20 mA
S/W : v02.40
Serial No : 22411C01
Range : 0 - 100
Units : %LEL
Sensor : Series 2000 Combustible
Gas : Methane
Tag : Vent 23C
First span : 21/07/97
Last span : 21/07/97
Cal. rem. : 06 months
A1 : 0020 %fsd
A2 : 0050 %fsd
A3 : 0075 %fsd
STEL
Threshold : 010.0 %fsd
Value : 0.000 %fsd
Time interval : 10 min.
LTEL
Threshold : 010.0 %fsd
Value : 0.000 %fsd
RATE
Threshold : 05.0 %fsd
Value : -0.074 %fsd
Max signal : 026.2 %fsd
Min signal : 000.0 %fsd
Present signal : 8.0 %fsd
Relay Interface : High Integrity
RL 1 Norm. energised
RL 2 Norm. de-energised
RL 3 Norm. de-energised
RL 4 Norm. de-energised
RL 5 Norm. de-energised
RL 6 Norm. de-energised
RL 7 Norm. de-energised
RL 8 Norm. de-energised
Notes: 1. The information printed will vary slightly depending on the
type of sensor drive module fitted to the channel card.
2. If an RS 232 device is not connected or is not able to accept
characters, the selected control card display will show XXXX.