Technical information

489www.fagerhult.com  •  www.fagerhult.co.uk
FSD
Output HF-std HF-dim
Column 1
All
HF-ballasts
Column 2
Some
HF-ballasts
Column 1
All
HF-ballasts
Column 2
Some
HF-ballasts
1x18 48 74 40 56
2x18 38 56 16 38
1x24 47 103 27 86
2x24 20 56 12 52
1x36 47 56 47 70
2x36 44 56 20 34
1x40 47 74 47 70
2x40 20 38 20 30
1x55 26 50 40 56
2x55 18 20 18 26
1x80 30 30 20 48
2x80 16 16 15 18
Additional comments
With fuse protection of luminaires, consideration should also be taken of the inrush • 
current as well as the combined rated current for the groups’ luminaires, the cable’s
cross-section and the average length of the group’s cabling.
The figures listed in the above tables assume a simultaneous ignition (same switch) at • 
the mains voltage peak value. 
The values in the tables apply for 1-pole miniature circuit breakers. When using multi-• 
pole miniature circuit breakers the number of luminaires should be reduced by 20 %. 
When using 16 A miniature circuit breakers with B characteristics the size of the • 
groups should be reduced by half. For 10 A miniature circuit breakers with C character-
istic the size of the group should be reduced by approximately 40 %. For exact sizing 
please contact our customer service team.
T8
Output HF-std HF-dim
Column 1
All
HF-ballasts
Column 2
Some
HF-ballasts
Column 1
All
HF-ballasts
Column 2
Some
HF-ballasts
1x18 48 122 47 86
2x18 48 75 20 70
3x18 20 80 24 56
4x18 20 56 20 38
1x36 47 82 47 70
2x36 37 56 20 56
1x58 47 60 40 56
2x58 20 26 20 30
1x70 34 47 - -
2x70 18 20 - -
FSM
Output HF-std HF-dim
Column 1 Column 2 Column 1 Column 2
All Some All Some
HF-ballasts HF-ballasts HF-ballasts HF-ballasts
1x13 34 118 40 40
2x13 34 116 60 60
1x14 47 94 47 47
2x14 47 94 47 47
1x17 47 94 47 47
2x17 47 94 47 47
1x18 35 152 38 70
2x18 35 128 26 48
1x26 33 144 38 70
2x26 20 102 20 46
1x32 33 124 38 50
2x32 20 82 20 26
1x42 33 124 38 50
2x42 20 82 12 26
1x57 36 94 22 38
2x57 17 17 - -
- = no current data available
FSQ
Output HF-std HF-dim
Column 1 Column 2 Column 1 Column 2
All Some All Some
HF-ballasts HF-ballasts HF-ballasts HF-ballasts
1x13 34 82 40 40
2x13 34 56 60 60
1x18 35 82 38 70
2x18 35 80 26 47
1x26 33 74 38 70
2x26 20 56 20 46
T5C
Output HF-std HF-dim
Column 1
All
HF-ballasts
Column 2
Some
HF-ballasts
Column 1
All
HF-ballasts
Column 2
Some
HF-ballasts
1x22 33 74 24 54
1x22+1x40 22 56 - -
1x40 33 74 24 54
1x55 47 50 20 34
1x60 47 47 20 20



/
  
For more information go to www.barbourproductsearch.info