Technical information

471www.fagerhult.com  •  www.fagerhult.co.uk
e-Sense smartSwitch On/O
– luminaires without dimmable HF-ballasts
Choices for occupancy detector:
Automatic ON/OFF (set time 1–30 minutes).• 
Not ON (when the lux level is above the set value) • 
Automatic OFF.
Choices for the Lux sensor:
Not ON with high lux level.• 
Manual modification of the lux level threshold • 
(50–2000 lx).
Note:
The luminaire does not have a dimmable HF-ballast, • 
the function is only ON/OFF.
Fagerhults Loop Light luminaire can be retro-fitted with
an end-cap inclusive of a smartSwitch sensor in an exist-
ing HF-std Loop Light; oering the ability to make sav-
ings via smartSwitch On/O in a pre-installed system.
e-Sense smartSwitch
–pendant 2 and 3-lamp luminaire with dimmable
HF-ballast
Choices for occupancy detector:
Automatic ON/OFF (set time 1–30 minutes).• 
Choices for manual control 2-lamp luminaire:
Pull cord ON/OFF and common control of the • 
Downlight/Uplight.
Choices for manual control 3-lamp luminaire:
Pull cord ON/OFF and control of the Downlight.• 
Pull cord ON/OFF and control of the Uplight.• 
Special functions:
The luminaire is equipped with an ECO-lp HF-ballast • 
with memory function when switched o.
Note:
Do not use the lux level setting. If the room is light and • 
the sensor does not ignite, the cord will not work.
e-Sense smartSwitch absence dampening
– luminaire with dimmable HF-ballast
Choices for occupancy detector:
Automatic absence dampening 100–10 % • 
(adjustable time 1–30 min).
Choices for the Lux sensor:
Not ON with high lux level.• 
Manual modification of the lux level threshold • 
(50–2000 lx).
Dimming
e-Sense smartSwitch
Occupancy detector
Presence control switches
the lighting on and o. After
the last presence detection
the light is automati-
cally switched o. The time
between detection and
switching o is adjustable,
1–30 minutes.
Lux level setting
Setting the threshold value
prevents the occupancy
detector reacting when
daylight is sucient.
Manual control
Manual control is only
available in smartSwitch
Dragdim luminaires.
Absence dampening
The occupancy detector
adjusts to a high light level
on detection and returns
to a low level after a short
period of time. No switch
o function.
Night: The oce is in darkness.
07:56 am: Automatic ignition.
Manual control of uplight and downlight.
The light is switched o according to the
time set on the sensor, approximately
15 minutes.
The light is set to a low basic level.
The light switches to a higher level when
presence is detected.
The delay after the last occupancy is short,
1–30 minutes.
After the set time, the light is adjusted
down to the basic level.
Combination manual/smartSwitch
smartSwitch with absence dampening
The images to the left show a combina-
tion of manual control and occupancy
detection. The graph demonstrates how
the energy consumption varies through-
out the course of the day.
The images to the left demonstrates
the dierent lighting scenarios which
occur during a working day. The graph
highlights how the energy use drops
significantly when Absence dampen-
ing is used. Depending on the type
of premises, it may be appropriate to
switch o the lighting completely dur-
ing the night using a time controller.
Energy 100 %
Energy 100 %



/
  
For more information go to www.barbourproductsearch.info