Technical information
463www.fagerhult.com • www.fagerhult.co.uk
Dimming
Phase control (impulse) – switchDIM, Touch DIM
L1
L2
L3
N
PE
DA/D1
DA/D2
Tridonic
PCA EXCEL one4all
orPCA ECO
switchDIM control and Smart LS II light sensors. HF-ballast PCA EXCEL One4all or PCA ECO.
Pulse switch
Tridonic
PCA ECO
Tridonic
PCA ECO
Tridonic
PCA ECO
Occupancy detector
Time setting
lux level
L1
L2
L3
N
PE
D1
D2
D1
D2
D1
D2
Pulse switch
switchDIM control with on/o function over occupancy detector
A retractable switch without indicator
lamp must be used. On/o and dim-
ming via the switch takes over control
from the Smart LS II sensor. Smart LS
II can only be connected to a Tridonic
HF-ballast. Default setting of the
required daylight value adjusted on
the sensor. The value can be changed
via the switch. The same phase must
be used for control and feeding the
HF-ballast. Neutral to the terminal block
DA/D1 can be looped internally in the
luminaire. If several HF-ballasts or more
advanced control is required, please
contact your Fagerhult representative.
The occupancy detector switches o
the light after the last occupancy and
a time delay. The light is switched on
at the last level, which can be o if the
light was switched o manually. A re-
tractable switch without indicator lamp
must be used. Maximum 25 HF-ballasts
can be connected to one control. The
same phase must be used for control
and feeding the HF-ballast. If several
HF-ballasts or more advanced control is
required, please contact your Fagerhult
representative.
L1
L2
L3
N
PE
D1
D2
Tridonic
PCA ECO
D1
D2
Tridonic
PCA ECO
D1
D2
Tridonic
PCA ECO
Pulse switch
switchDIM control with retractable switch HF-ballast PCA ECO
A retractable switch without indicator
lamp must be used. Maximum 25
HF-ballasts can be connected to one
control. The same phase must be used
for control and feeding the HF-ballast.
If several HF-ballasts or more advanced
control is required, please contact your
Fagerhult representative.
/