Specifications
14
DIGICOM / DIGIHP THERMOSTATS
DESCRIPTION
The Zonex Systems DIGICOM (2H, 2C) and DIGIHP (3H, 2C) are
microprocessor based, auto changeover, stand-alone thermostats used to
control stand alone units with no dampers in the system. The DIGICOM is
the Gas Electric version and has two-stage heat / cool outputs with
selectable fan operation. The DIGIHP Heat Pump thermostats have two-
stage cool and three-stage heat outputs with selectable fan. The DIGICOM
and DIGIHP thermostats have a large, easy-to-read LCD display with a
distinctive grey backlight. The display backlight is continuously illuminated
in the Occupied mode and goes off in the Unoccupied mode.
The DIGICOM and DIGIHP are very easy to configure through the system program or to make
manual adjustments using the buttons located on the front cover.
These thermostats feature an onboard thermistor for precise temperature measurement. In the
event of power loss, the Heat and Cool set points are stored in a non-volatile memory, without the
need for battery backup.
The space ambient temperature is continually displayed with large, easy-to-read numbers. The
DIGICOM temperature display range is 45° - 95°F (7°- 35°C) and the DIGIHP temperature display
range is 55°- 95°F (12°- 35°C). Fan Mode, Heat or Cool set points and operation modes are all
indicated on the display.
Programmed set points can be manually adjusted at the thermostat or electronically locked through
the system program to provide limited manual set point adjustment. Two-hour override is provided
for after-hours temporary operation with a touch of a button.
INSTALLATION
Thermostat and terminal base
1. The thermostat is to be installed on the interior wall, away from drafts, supply air currents and
direct sunlight or any heat generating source.
2. To remove the thermostat cover, grasp the cover at the top and pull straight off; do not pivot the
cover from the base.
3. Install the thermostat terminal base to the wall using the provided anchors and screws. The
thermostat can also be mounted on a 2x4 electrical box using two #6-32” screws.
Wiring
The Zonex Systems DIGICOM and DIGIHP thermostats have been specifically designed to make
wall mounting and wire connections very easy. The thermostat terminal base has two separate
terminal blocks: the left side terminal block is for the 24vac control circuits, and the right side
terminal block is for the RX TX communication circuits. There are two sets of RX TX terminals on
the base to make daisy chain wiring from device to device straightforward and simple.