11
Configuration
Addressing
Each thermostat must have a unique address from 1-17.
1. Press and hold the Menu button until you see the system mode display on the lower right begin
to change modes; then press and hold the Heat/Cool button with the Menu button.
2. When the display shows “address,” release the Menu and Heat/Cool buttons, and press the UP
or DN button until the correct address is displayed in the upper right of the display.
3. After setting the address, the thermostat will automatically go back to normal operation; and the
set point temperature will replace the address number just programmed.
Display Temperature Calibration
Thermostats are calibrated at the factory and should require no further adjustment. However, the
display space temperature may be field calibrated by the following procedure:
1. Press and hold the Heat/Cool and Select buttons together; then press and release the UP
button to increase the display temperature by one degree.
2. To lower the temperature display, press the DN button once, after pressing the Heat/Cool and
Select buttons. This makes a 1-degree change.
Adjusting Set Points
The Heat or Cool set points can be displayed by pressing the Heat/Cool button; the set point will be
indicated on the upper right of the display.
The Heat and Cool set points can be individually set for the Occupied and Unoccupied modes.
Occupied Mode: H & C settings - Function switch (L) in the DAY position, or time clock in
Occupied.
Unoccupied Mode: H & C settings – Function switch (L) in the NIGHT position, or time clock
in Unoccupied.