set switches
Chapter 2  Command Descriptions  209
Options range=range
The port or range of ports to which this command applies.
mode={232|485}
Selects the electrical interface of the serial port. The selected value 
determines whether the "wires" and "termination" options are meaningful.
232
The serial port uses electrical interface EIA-232. This interface uses 
independent wires to transmit and receive data, which allows data to 
be sent and received between devices simultaneously.
485
The serial port uses electrical interface EIA-485. This mode can also 
be used for EIA-422 connections. This interface uses two wires to both 
transmit and receive data. This interface also allows for multiple 
transmitters and receivers to be easily connected together.
The "wires" and "termination" command options specifically apply to 
serial ports in EIA-485 mode.
The default is "232." 
wires={two|four}
Applies when the serial port is running in EIA-485 mode only. Selects the 
number of differential wires used for communication and implicitly 
determines the duplex of the connection.
two
The serial port operates in two-wire mode. This mode is a half-duplex 
connection with shared transmit and receive wires.
four
The serial port operates in four-wire mode. This mode is a full-duplex 
connection with independent transmit and receive pairs.
The default is "four." 
termination={on|off}
Applies when the serial port is running in EIA-485 mode only. Determines 
whether termination and biasing resistors are used across the lines. 
on
Termination and biasing resistors are enabled across the lines.
Termination should be set to "on" if this node is an endpoint of the 485 
network. Biasing should be used in at least one unit in a two-wire 
environment.
off
Termination and biasing resistors are disabled across the lines.
The default is "off."