Specifications

RTS Operation G-4
The ID command is write protected and checksums are not supported. The
module will abandon any ID command with a message length in excess of
16 characters.
Command: $1IDBOILER ROOM
Response: *
Command: #1IDBOILER ROOM
Response: *1IDBOILER ROOM02
Read IDentification (RID)
The Read Identification (RID) command is used to read data previously
stored by the ID command. The RID command response message length
is variable depending on the stored message length. The maximum re-
sponse length can be up to 25 characters using the long form prompt and
linefeeds enabled.
Command: $1RID
Response: *BOILER ROOM
Command: #1RID
Response: *1RIDBOILER ROOM54
Read Time Delay 1 (RT1)
The RT1 command is used to read the time delay value previously stored
with the T1 command. The value returned is scaled in milliseconds and has
a range of 0 to 2000ms.
Command: $1RT1
Response: *+00100.00
Command: #1RT1
Response: *1RT1+00100.00DC
Read Time Delay 2 (RT2)
The RT2 command is used to read the time delay value previously stored
with the T2 command. The value returned is scaled in milliseconds and has
a range of 0 to 2000ms.
Command: $1RT2
Response: *+00550.00