Specifications

Continuous Operation F-3
execute the S1000 utility software (filename = 100030.exe). At the main
menu, select HOST and specify the correct serial computer port. All
remaining host values should not have to be changed. Press <ESC> key
and return to main menu when port selection is complete.
Step 2. Select main menu “SETUP” and enter a module address and
model number. If the module “DEFAULT*” pin is grounded (connected to
GND terminal) then enter address “1” and press <ENTER>. Enter the
correct model number located on the module label and press <ENTER>.
The module setup information will then be read and displayed for editing.
The Baud Rate value is the only value that must change in most cases.
With the mouse pointer, double-click on the Baud Rate box and incre-
ment to the desired value. Press the “+” key to increment the value if a
mouse is not available. After the value has been changed, depress the
<F10> function key to download the new setup value. Press “N” not to
reset the remote device. The analog input module is now configured.
Press the <ESC> key and return to the main menu. Turn the module
power supply off and remove the black screw terminal plug from the side
of the analog input module.
Step 3. Plug the screw terminal plug, that is connected to the computer,
into the side of the analog output module and turn the power supply on.
Select main menu “SETUP” and re-enter the address and new model
number. If the “DEFAULT*” pin is grounded, enter address “1” and press
<ENTER>. Enter the analog output module model number and press
<ENTER>.
The Baud Rate value and “Continuous Enabled” bit are the only values
that must change in most cases. With the mouse pointer, double-click on
the Baud Rate box and increment to the desired value. Double-click on
the “Continuous Input” selection box to “enable” that option. Press the “+”
key to increment either value if a mouse is not available. After the values
have been changed, depress the <F10> function key to download the
new values. Press “N” not to reset the remote device.
The analog output module is now configured. Press the <ESC> key and
return to the main menu. Turn the module power supply off and remove
the black screw terminal plug from the side of the analog output module.
Both modules are now properly configured.