Specifications
Command Set 4-8
or SetPoint (SP) command.
Command: $1CZ
Response: *
Command: #1CZ
Response: *1CZF8
Disable Alarms (DA)
Most D1000 modules feature LO/DO0 and HI/DO1 pins on the module
connector. These pins serve a dual function and can be used to output either
the alarm outputs or digital outputs 0 and 1. The Disable Alarms command
is used to connect the digital outputs 0 and 1 to the connector pins. The alarm
settings are not affected in any way except that the alarm outputs are
disconnected from the module connector. The alarm status can still be read
with the Digital Input (DI) command. The complement to the DA command
is the Enable Alarms (EA) command.
Command: $1DA
Response: *
Command: #1DA
Response: *1DAE0
Digital Input (DI)
The DI command reads the status of the digital inputs and the alarms. The
response to the DI command is four hex characters representing two bytes
of data. The first byte contains the alarm status. The second byte contains
the digital input data.
Command: $1DI
Response: *0003
Command: #1DI
Response: *1DI0003AB
Listed below are the four possible alarm states in the first digital input byte
and their hex values.
00 Both HI and LO alarms off.
01 HI alarm off. LO alarm on.
02 HI alarm on. LO alarm off.
03 Both HI and LO alarms on.
The second byte displays the hex value of the digital input status. The
number of digital inputs varies depending on module type.
Digital Inputs DI7 DI6 DI5 DI4 DI3 DI2 DI1 DI0
Data Bits 76543210