Installation Guide

Rubix Suspended Installation
DIL-0114-0003 Revision - J 31/01/2023
Through-wire
(ST / TW / ER)
220-240V / 50-60Hz
IP20
1.
2.
3.
4.
5.
6.
Firstly check fitting type is correct before installation
through-wire versions have cable cut-outs in ends
and threaded holes for joining bracket / end plate
Standalone
To make electrical connection, loosen thumbnut,
remove / lift away cover plate. Pass cable through
entry gland and connect to appropriate terminations
Secure suspension
drops as shown in
marked positions.
Screw suspension
wire and clutch into
ceiling fixture.
Insert toggles of Y
suspension kit in to 7mm
holes in luminaire
To attach to main
wire, depress top of
clutch & insert wire
1800/1500/1260
When mounting continuously, STARTER should have x2
suspensions. Subsequent TW fittings require just one…
If preferred, each fitting CAN have 2 suspensions fitted (at
same centres as STARTER). NOTE, if custom infill pieces are
specified, positions of suspensions will be different always
check before installation!!
WARNING: Luminaire must be earthed. Risk of electric shock from LED boards if operated with cover
removed. Installation / operation outside of luminaires intended scope invalidates warranty. Suitable only for
domestic / light industrial / industrial applications within the scope of EN55015. Tested to compliance with
BSEN 60598: specification for general requirements and tests. Must be installed by a suitably qualified person
in accordance with all relevant legislation. Ambient operating temperature of 0°C to 25°C. If maximum
operating temperature is exceeded luminaire will automatically dim / switch off. Terminal blocks are rated to
16A unless stated otherwise. The light source contained in this luminaire shall only be replaced by the
manufacturer or his service agent or a similar qualified person. LUMINAIRES WITH EMERGENCY PACK:
When supply is isolated battery output terminals may be live if battery is connected. Isolate mains and battery
before servicing. Emergency luminaires require unswitched live connection taken from same phase as
switched supply. When unswitched supply is connected status indicator illuminates green, when unswitched
supply is disconnected indicator extinguishes and luminaire operates in emergency mode. 24 hour charge
period required before undertaking full discharge test. Emergency test sheets provided should be used to
record all emergency tests. Batteries should be replaced when 3 hour duration is not met. Excessive switching
of permanent live may result in premature battery failure. Battery electrolyte can be harmful to eyes / open
wounds, do not puncture, if electrolyte touches skin / eyes flush with water. Do not incinerate batteries.
Terminal Labelling:
Power
L1 Switched Live
E Earth
N Neutral
Emergency
L2 Unswitched Live
DA/AT3 DALI Autotest
DA/AT3 DALI Autotest
Dimming
-/D1/DA Analogue/DSI/DALI
+/D2/DA Analogue/DSI/DALI
L3 Switch Dim /
Corridor Function