The DC supply must meet the following requirements for proper operation of the
Sensor Node:
1. DC Output Voltage Range: 24 VDC +/-10%
2. DC Output Current: 1.0 A Minimum
3. Supply must be an NEC Class II power supply that is certified as a
Limited Power Source (LPS)
The cabling used to connect the external DC supply to the Sensor Node DC power
connector must comply with the following requirements:
1. Connector on Sensor Node end of power cable must be a 4-socket
M8 style connector that will mate with: Phoenix Contact - 1453481
2. Cabling must comply with Article 725 of the NEC for Class 2
circuits
1.2.2.5. Power Supply Installation
(TBD)
1.2.2.6. Sensor Connections
The Fluid Interface provides two ports for connection to external sensors that
monitor the properties of the hydraulic fluid in the system. Cables for connecting
the external sensors are included with the system.