- 6 Functional description in detail
- 7 Service / CO2 sensor calibration
- 8 Device labels
- 9 FCC (United States) Regulatory Statement
- 10 ISED (Canada) Regulatory Statements
- 11 Ordering information
- 12 Revision history
EnoPuck
®
CO2 / CO2 NOISE / CO2 WALL
Product manual Page 24 of 32
© DEUTA Controls GmbH Paffrather Str. 140, 51465 Bergisch Gladbach Tel.:+49 2202 285 57- 61
23.11.2022 Hauptstraße 76, 32479 Hille Tel: +49 5734 51466 - 0
Technical data might change info@deuta-controls.de; www.deuta-controls.dnet Fax:+49 5734 51466 - 28
Figure 5: Service button of EnoPuck® CO2 WALL
7.2.2 Room without windows that can be opened
If you can not open the windows of the room where the EnoPuck
®
CO2 WALL is
mounted, or there are simply no windows in the room, you have to go somewhere
where you can open the windows to have fresh air for calibration procedure.
The in-wall power supply is line powered!
De-energize the in-wall power supply before to dismount the EnoPuck
®
CO2 WALL.
Dismount the EnoPuck
®
CO2 WALL from the bracket, and then disconnect the 12 V
DC power plug in between the EnoPuck CO2 WALL and the in-wall power supply.
To be able to re-calibrate, you will need an external power supply with the correct
power connector (round, 2.1 x 5.5 mm, male).
The process for re-calibration ist the same as described above.
After re-calibration, connect the power plug again, and re-mount the EnoPuck CO2
WALL to the wall-mount bracket.