Product Info
Table Of Contents
- 1.1 About this manual
- 1.2 Notes about this Manual
- 1.3 Validity of this documentation
- 1.4 Symbols / Information on safety
- 2 Information on product safety
- 3 Disposal
- 4 Device description
- 5 Technical data
- 5.1 Communication / EnOcean wireless interface
- 5.2 Sensor: CO2 concentration
- 5.3 Sensor: Rel. humidity (RH)
- 5.4 Sensor: Temperature
- 5.5 Sensor: Ambient light / brightness
- 5.6 Sensor: Sound pressure level (only EnoPuck® CO2 NOISE)
- 5.7 Sensor: Motion / PIR
- 5.8 User interfaces
- 5.9 Housing / connection technology
- 5.10 Power supply
- 5.11 Environmental conditions
- 5.12 Dimensions and weight
- 5.13 Approvals
- 5.14 Standards and guidelines
- 6 Functional description in detail
- 7 Service / CO2 sensor calibration
- 8 Device labels
- 9 FCC (United States) Regulatory Statement
- 10 ISED (Canada) Regulatory Statements
- 11 Ordering information
- 12 Revision history
EnoPuck
®
CO2 / CO2 NOISE / CO2 WALL
Product manual Page 23 of 32
© DEUTA Controls GmbH Paffrather Str. 140, 51465 Bergisch Gladbach Tel.:+49 2202 285 57- 61
23.11.2022 Hauptstraße 76, 32479 Hille Tel: +49 5734 51466 - 0
Technical data might change info@deuta-controls.de; www.deuta-controls.dnet Fax:+49 5734 51466 - 28
4. After 2 seconds the LED’s will start flashing red. This signals that calibration will be
carried out if you continue to hold the Service Button. If you release the Service button
now, the process will be canceled.
4. After 6 seconds the LEDs will start to flash blue. The calibration process starts and
will take 10 minutes. You can now release the button now.
5. Wait until the process is finished. The purpose of the waiting time is to create the
same CO2 concentration inside the housing as in the outside air. At the end of the
time, the value then measured is used as the reference value of 400 ppm. This is the
typical CO2 concentration in the outside air.
6. As soon as the calibration has been successfully completed, the EnoPuck
®
CO2 /
EnoPuck
®
CO2 NOISE L lights up green continuously.
7. Disconnect the device from the power supply. After the restart, the EnoPuck
®
CO2 /
EnoPuck
®
CO2 NOISE is ready for operation again.
8. In the event of an error, it lights up red continuously. Please disconnect the
EnoPuck
®
CO2 / EnoPuck
®
CO2 NOISE from the power supply and repeat the
calibration process again.
Avoid mechanical impact after re-clibration!
Any mechanical stress between calibration and finally mounting of the
EnoPuck
®
CO2 / EnoPuck
®
CO2 NOISE might again influence
calibration.
7.2 Re-calibration of EnoPuck
®
CO2 WALL
7.2.1 Room with windows that can be opened
If you can open windows in the room where the EnoPuck
®
CO2 WALL is mounted,
open the window for at least 15 minutes, so the air inside the room will have the same
CO2 concentration as the air outside.
The start calibration process as describerd above.You can leave the EnoPuck
®
CO2
WALL mounted to the wall. Push the service button while it is mounted on the wall-
bracket.