Product Info
Table Of Contents
- 1.1 About this manual
- 1.2 Notes about this Manual
- 1.3 Validity of this documentation
- 1.4 Symbols / Information on safety
- 2 Information on product safety
- 3 Disposal
- 4 Device description
- 5 Technical data
- 5.1 Communication / EnOcean wireless interface
- 5.2 Sensor: CO2 concentration
- 5.3 Sensor: Rel. humidity (RH)
- 5.4 Sensor: Temperature
- 5.5 Sensor: Ambient light / brightness
- 5.6 Sensor: Sound pressure level (only EnoPuck® CO2 NOISE)
- 5.7 Sensor: Motion / PIR
- 5.8 User interfaces
- 5.9 Housing / connection technology
- 5.10 Power supply
- 5.11 Environmental conditions
- 5.12 Dimensions and weight
- 5.13 Approvals
- 5.14 Standards and guidelines
- 6 Functional description in detail
- 7 Service / CO2 sensor calibration
- 8 Device labels
- 9 FCC (United States) Regulatory Statement
- 10 ISED (Canada) Regulatory Statements
- 11 Ordering information
- 12 Revision history
EnoPuck
®
CO2 / CO2 NOISE / CO2 WALL
Product manual Page 22 of 32
© DEUTA Controls GmbH Paffrather Str. 140, 51465 Bergisch Gladbach Tel.:+49 2202 285 57- 61
23.11.2022 Hauptstraße 76, 32479 Hille Tel: +49 5734 51466 - 0
Technical data might change info@deuta-controls.de; www.deuta-controls.dnet Fax:+49 5734 51466 - 28
7 Service / CO2 sensor calibration
Do not open the housing / no serviceable parts inside
There are no serviceable parts inside the product. Do not open the
housing. Otherwise warranty will be void, and electronic components might
be damaged.
If the EnoPuck
®
CO2 / EnoPuck
®
CO2 NOISE / EnoPuck
®
CO2 WALL has been exposed
to mechanical stress such as impact, strong vibration or a fall, the measurement of the CO2
value may no longer be correct.
7.1 Re-calibration of EnoPuck
®
CO2 / EnoPuck
®
CO2 NOISE
Due to several reasons, the devices have no auto-calibration feature enabled.
To recalibrate them manually, please proceed as follows:
1. Find a suitable location where the EnoPuck
®
CO2 / EnoPuck
®
CO2 NOISE can
measure CO2 outside air (no drafts). Make sure that the device is never exposed to
moisture or rain.
2. Supply the device via the external +12 V DC power supply. Do not disconnect the
power supply until the end of the process.
3. Press and hold the Service button.