Product Info
Table Of Contents
- 1.1 About this manual
- 1.2 Notes about this Manual
- 1.3 Validity of this documentation
- 1.4 Symbols / Information on safety
- 2 Information on product safety
- 3 Disposal
- 4 Device description
- 5 Technical data
- 5.1 Communication / EnOcean wireless interface
- 5.2 Sensor: CO2 concentration
- 5.3 Sensor: Rel. humidity (RH)
- 5.4 Sensor: Temperature
- 5.5 Sensor: Ambient light / brightness
- 5.6 Sensor: Sound pressure level (only EnoPuck® CO2 NOISE)
- 5.7 Sensor: Motion / PIR
- 5.8 User interfaces
- 5.9 Housing / connection technology
- 5.10 Power supply
- 5.11 Environmental conditions
- 5.12 Dimensions and weight
- 5.13 Approvals
- 5.14 Standards and guidelines
- 6 Functional description in detail
- 7 Service / CO2 sensor calibration
- 8 Device labels
- 9 FCC (United States) Regulatory Statement
- 10 ISED (Canada) Regulatory Statements
- 11 Ordering information
- 12 Revision history
EnoPuck
®
CO2 / CO2 NOISE / CO2 WALL
Product manual Page 20 of 32
© DEUTA Controls GmbH Paffrather Str. 140, 51465 Bergisch Gladbach Tel.:+49 2202 285 57- 61
23.11.2022 Hauptstraße 76, 32479 Hille Tel: +49 5734 51466 - 0
Technical data might change info@deuta-controls.de; www.deuta-controls.dnet Fax:+49 5734 51466 - 28
6 Functional description in detail
6.1 Basic device description
The EnoPuck
®
CO2 / EnoPuck
®
CO2 NOISE / EnoPuck
®
CO2 WALL is basically a
multi sensor with integrated LEDs. Each sensor can be configured to be switched off,
or to send the measured value in a fixed timed interval.
6.2 Send Teach-In telegrams
To be able to use standardized EEP (EnOcean Equipment Profiles), the EnoPuck
®
CO2 / EnoPuck
®
CO2 NOISE / EnoPuck
®
CO2 WALL can send all data in a
sequence, using different ID’s and different EEP’s.
To connect to any building automation system, a so called Teach-In telegram will be
send by the device using the Service button.
Figure 4: Location of Service buttons
The button is located on the side, approx. 3 cm to the right of the socket for the plug-in
power supply, and can be operated with a paper clip.
6.2.1 CO2 Teach-In (A5-09-04)
If the button is pressed 1x briefly within 2 seconds, a learning telegram for the EEP
A5-09-04 is sent after the 2 seconds have elapsed.