5 Technical data
5.1 Communication / EnOcean wireless interface
Type
EnOcean
Number
1
Transmit / receive center frequency 902.875 MHz
Maximum transmission power +94 dBµV/m
Table 2: Technical data / communication
5.2 Sensor: CO2 concentration
Measuring range
0 .. 2.550 ppm (with MSC instead of standard
EEP up to 10.000 ppm, on request)
Accuracy
± 30 ppm + 3% MV
(@ 25 °C, range 400 – 2.550 ppm)
Repeatability 10 ppm
Temperature stab. 2,5 ppm / °C
Response time Typ. 25 s
Table 3: Technical data CO2
5.3 Sensor: Rel. humidity (RH)
Measuring range
0 100 %
accuracy
± 2 %
Repeatability 0,1 %
Response time
Typ. 8 s
Table 4: Technical data RH
5.4 Sensor: Temperature
Measuring range
- 40 120 °C
Accuracy
± 0,5 °C
Repeatability 0,1 °C