Manual Page 1 of 32 EnoPuck® CO2 EnoPuck® CO2 NOISE EnoPuck® CO2 WALL EnOcean Sensor and RGB-LED for CO2 and sound pressure level measurement EnOcean / 902 MHz / FCC Version 1.02 © DEUTA Controls GmbH Paffrather Str. 140, 51465 Bergisch Gladbach Tel.:+49 2202 285 57- 61 23.11.2022 Hauptstraße 76, 32479 Hille Tel: +49 5734 51466 - 0 Technical data might change info@deuta-controls.de; www.deuta-controls.
EnoPuck® CO2 / CO2 NOISE / CO2 WALL Product manual Page 2 of 32 © 2022 DEUTA Controls GmbH All rights reserved This manual, including all figures and illustrations, is copyright-protected. Any further use of this manual by third parties that violate pertinent copyright provisions is prohibited. Reproduction, translation, electronic and phototechnical filing/archiving (e.g., photocopying) as well as any amendments require the written consent of DEUTA Controls GmbH, Bergisch Gladbach, Germany.
EnoPuck® CO2 / CO2 NOISE / CO2 WALL Product manual Page 3 of 32 Table of contents 2 1.1 About this manual ................................................................................................... 6 1.2 Notes about this Manual .......................................................................................... 6 1.3 Validity of this documentation .................................................................................. 7 1.4 Symbols / Information on safety ................
EnoPuck® CO2 / CO2 NOISE / CO2 WALL Product manual 6 5.7 Sensor: Motion / PIR ..............................................................................................18 5.8 User interfaces .......................................................................................................18 5.9 Housing / connection technology ............................................................................18 5.10 Power supply......................................................................
EnoPuck® CO2 / CO2 NOISE / CO2 WALL Product manual Page 5 of 32 0x00012345 .................................................................................................................27 EnoPuck® CO2 WALL / FCC (AL-602-04-902) / Part. Nr. 12564 ............................28 8.3 9 8.3.1 Device / certification data: ...............................................................................28 8.3.2 Label 1: ......................................................................................
EnoPuck® CO2 / CO2 NOISE / CO2 WALL Product manual 1.1 Page 6 of 32 About this manual This Manual describes the products • EnoPuck® CO2 / FCC (AL-602-01-092) / Part nr. 12562 • EnoPuck® CO2 NOISE / FCC (AL-602-02-902) / Part nr. 12563 • EnoPuck® CO2 WALL / FCC (AL-602-04-902) / Part. Nr. 12564 (also referred to as "PRODUCT" in this document). These operating instructions are part of the product. • You may only use the product if you have fully read and understood this manual.
EnoPuck® CO2 / CO2 NOISE / CO2 WALL Product manual Page 7 of 32 Technical terms in this documentation The technical terms used in this documentation are available in the glossary at the end of the manual. 1.3 Validity of this documentation This documentation applies ot the following products: • EnoPuck® CO2 / FCC (AL-602-01-092) / Part nr. 12562 • EnoPuck® CO2 NOISE / FCC (AL-602-02-902) / Part nr. 12563 • EnoPuck® CO2 WALL / FCC (AL-602-04-902) / Part. Nr.
EnoPuck® CO2 / CO2 NOISE / CO2 WALL Product manual 1.4 Page 8 of 32 Symbols / Information on safety The symbols in this is document and their meaning are as follows: Personal Injury! Indicates a high-risk, imminently hazardous situation which, if not avoided, will result in death or serious injury. Personal Injury Caused by Electric Current! Indicates a high-risk, imminently hazardous situation which, if not avoided, will result in death or serious injury.
EnoPuck® CO2 / CO2 NOISE / CO2 WALL Product manual Page 9 of 32 Damage to Property caused by Electrostatic Discharge (ESD)! Indicates a potentially hazardous situation which, if not avoided, may result in damage to property. Important Note! Indicates a potential malfunction which, if not avoided, however, will not result in damage to property. Additional Information: Refers to additional information which is not an integral part of this documentation (e.g., the Internet).
EnoPuck® CO2 / CO2 NOISE / CO2 WALL Product manual 2.2 Page 10 of 32 Predictable incorrect application The products EnoPuck® CO2 / EnoPuck® CO2 NOISE / EnoPuck® CO2 WALL must never be used in the following cases and for the following purposes: Personal Injury! Products must never be used solely or in conjunction with devices which are used for health-saving or life-saving purposes, or whose operation may incur hazards to humans, animals orproperty.
EnoPuck® CO2 / CO2 NOISE / CO2 WALL Product manual Page 11 of 32 Do not use for health-saving or life-saving purposes! In conjunction with devices which are used for health-saving or life-saving purposes or whose operation may incur hazards to humans, animals or property! 2.3 Qualification of personnel 2.3.1 EnoPuck® CO2 / EnoPuck® CO2 NOISE These products are powered by an external power supply with +12 V DC. There is no special training necessary to use them.
EnoPuck® CO2 / CO2 NOISE / CO2 WALL Product manual Page 12 of 32 3 Disposal Electrical and electronic equipment may not be disposed of with household waste. This also applies to products without this symbol. Electrical and electronic equipment contain materials and substances that can be harmful to the environment and health. Electrical and electronic equipment must be disposed of properly after use. Note only for EU: WEEE 2012/19/EU applies throughout Europe. Directives and laws may vary nationally.
EnoPuck® CO2 / CO2 NOISE / CO2 WALL Product manual Page 13 of 32 4 Device description 4.1 Functionality The EnoPuck® CO2 / EnoPuck® CO2 NOISE / EnoPuck® CO2 WALL is basically a multi sensor with integrated LEDs. Each sensor can be configured separately to be switched off, or to send the measured value in a fixed timed interval. 4.
EnoPuck® CO2 / CO2 NOISE / CO2 WALL Product manual 4.4 Page 14 of 32 Factory settings The basic configuration of an EnoPuck® CO2 / EnoPuck® CO2 NOISE / EnoPuck® CO2 WALL is actually as follows: EnoPuck® Color Level R/red [%] Level green/G [%] Green 0 4 0 Yellow 10 7 0 Orange 6 1 0 Enabled Transmit interval EnoPuck® Sensor Level blue/B [%] CO2 / Temp.
EnoPuck® CO2 / CO2 NOISE / CO2 WALL Product manual Page 15 of 32 Figure 1: External interfaces EnoPuck® CO2 / CO2 NOISE 4.5.
EnoPuck® CO2 / CO2 NOISE / CO2 WALL Product manual Page 16 of 32 Figure 3: External power connection and mounting knobs EnoPuck® FCC WALL 4.6 Observe intended use The EnoPuck® CO2 / EnoPuck® CO2 NOISE / EnoPuck® CO2 WALL must not be used in any relation with equipment that supports, directly or indirectly, human health or life or with applications that can result in danger for people, animals or real value. 4.7 Observe statutory provisions for operating frequency range.
EnoPuck® CO2 / CO2 NOISE / CO2 WALL Product manual Page 17 of 32 5 Technical data 5.1 Communication / EnOcean wireless interface Type EnOcean Number 1 Transmit / receive center frequency 902.875 MHz Maximum transmission power +94 dBµV/m Table 2: Technical data / communication 5.2 Sensor: CO2 concentration Measuring range 0 .. 2.550 ppm (with MSC instead of standard EEP up to 10.000 ppm, on request) Accuracy ± 30 ppm + 3% MV (@ 25 °C, range 400 – 2.
EnoPuck® CO2 / CO2 NOISE / CO2 WALL Product manual Page 18 of 32 Response time Typ. 2 s Table 5: Technical data temperature 5.5 Sensor: Ambient light / brightness Measuring range 0 – 64.000 lux Accuracy ± 10 % Table 6: Technical data ambient light sensor 5.6 Sensor: Sound pressure level (only EnoPuck® CO2 NOISE) Measuring range -30 .. -80 dBSPL Accuracy ± 10 % Table 7: Technical data sound pressure level 5.7 Sensor: Motion / PIR Detection angle 120 degrees Detection range 0.
EnoPuck® CO2 / CO2 NOISE / CO2 WALL Product manual Page 19 of 32 Typ. 1.5 W, ma. 5 W (depends on LED configuration) Power consumption Table 11: Technical data / power supply 5.11 Environmental conditions Operating temp. 0°.. 50 °C Storage temp. -20 ..+70 °C Rel. humidity 0..95 % rel. humidity, non condensing Protection class IP20 Table 12: Technical data / environmental conditions 5.
EnoPuck® CO2 / CO2 NOISE / CO2 WALL Product manual Page 20 of 32 6 Functional description in detail 6.1 Basic device description The EnoPuck® CO2 / EnoPuck® CO2 NOISE / EnoPuck® CO2 WALL is basically a multi sensor with integrated LEDs. Each sensor can be configured to be switched off, or to send the measured value in a fixed timed interval. 6.
EnoPuck® CO2 / CO2 NOISE / CO2 WALL Product manual Page 21 of 32 6.2.2 PIR Teach-In (A5-07-01) If the button is pressed 2x briefly within 2 seconds, a learning telegram for the EEP A5-07-01 is sent after the 2 seconds have elapsed. Brightness Teach-In (A5-08-01) 6.2.3 If the button is pressed 3x briefly within 2 seconds, a learning telegram for the EEP A5-08-01 is sent after the 2 seconds have elapsed. Sound Pressure Level Teach-In (D2-14-52) 6.2.
EnoPuck® CO2 / CO2 NOISE / CO2 WALL Product manual Page 22 of 32 7 Service / CO2 sensor calibration Do not open the housing / no serviceable parts inside There are no serviceable parts inside the product. Do not open the housing. Otherwise warranty will be void, and electronic components might be damaged. If the EnoPuck® CO2 / EnoPuck® CO2 NOISE / EnoPuck® CO2 WALL has been exposed to mechanical stress such as impact, strong vibration or a fall, the measurement of the CO2 value may no longer be correct.
EnoPuck® CO2 / CO2 NOISE / CO2 WALL Product manual Page 23 of 32 4. After 2 seconds the LED’s will start flashing red. This signals that calibration will be carried out if you continue to hold the Service Button. If you release the Service button now, the process will be canceled. 4. After 6 seconds the LEDs will start to flash blue. The calibration process starts and will take 10 minutes. You can now release the button now. 5. Wait until the process is finished.
EnoPuck® CO2 / CO2 NOISE / CO2 WALL Product manual Page 24 of 32 Figure 5: Service button of EnoPuck® CO2 WALL 7.2.2 Room without windows that can be opened If you can not open the windows of the room where the EnoPuck® CO2 WALL is mounted, or there are simply no windows in the room, you have to go somewhere where you can open the windows to have fresh air for calibration procedure. The in-wall power supply is line powered! De-energize the in-wall power supply before to dismount the EnoPuck® CO2 WALL.
EnoPuck® CO2 / CO2 NOISE / CO2 WALL Product manual Page 25 of 32 Avoid mechanical impact after re-clibration! Any mechanical stress between calibration and finally mounting of the EnoPuck® CO2 WALL might again influence calibration. Finally. power up the in-wall power supply. The EnoPuck CO2 WALL should re-start immediately. 8 Device labels The following labels are placed on the bottom side of the devices: © DEUTA Controls GmbH Paffrather Str. 140, 51465 Bergisch Gladbach Tel.:+49 2202 285 57- 61 23.
EnoPuck® CO2 / CO2 NOISE / CO2 WALL Product manual 8.1 Page 26 of 32 EnoPuck® CO2 / FCC (AL-602-01-092) / Part nr. 12562 8.1.1 Device / certification data: Model name: * AL-602-01-902 EnoPuck CO2 / FCC Order number: * 12562 FCC ID: * 2AZTH-AL-602-XX-902 IC certification number: * 27242-602XX902 PMN: * 12562 AL-602-01-902 HVIN: * 12562 AL-602-01-902 FVIN: * 1.0 8.1.2 Label 1: FCC ID: 2AZTH-AL-602-XX-902 IC: 27242-602XX902 ewq 12562 AL-602-01-902 AL-602-01-902 EnoPuck CO2 / RoHS 8.1.
EnoPuck® CO2 / CO2 NOISE / CO2 WALL Product manual 8.2 Page 27 of 32 EnoPuck® CO2 NOISE / FCC (AL-602-02-902) / Part nr. 12563 8.2.1 Device / certification data: Model name: * AL-602-02-902 EnoPuck CO2 NOISE / FCC Order number: * 12563 FCC ID: * 2AZTH-AL-602-XX-902 IC certification number: * 27242-602XX902 PMN: * 12563 AL-602-02-902 HVIN: * 12563 AL-602-02-902 FVIN: * 1.0 8.2.
EnoPuck® CO2 / CO2 NOISE / CO2 WALL Product manual 8.3 Page 28 of 32 EnoPuck® CO2 WALL / FCC (AL-602-04-902) / Part. Nr. 12564 8.3.1 Device / certification data: Model name: * AL-602-04-902 EnoPuck WALL / FCC Order number: * 12564 FCC ID: * 2AZTH-AL-602-XX-902 IC certification number: * 27242-602XX902 PMN: * 12564 AL-602-04-902 HVIN: * 12564 AL-602-04-902 FVIN: * 1.0 8.3.
EnoPuck® CO2 / CO2 NOISE / CO2 WALL Product manual Page 29 of 32 9 FCC (United States) Regulatory Statement This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: 1. This device may not cause harmful interference, and 2. This device must accept any interference received, including interference that may cause undesired operation.
EnoPuck® CO2 / CO2 NOISE / CO2 WALL Product manual Page 30 of 32 11 Ordering information Part name Part nr. AL-602-01-902 EnoPuck CO2 / FCC AL-602-02-902 EnoPuck CO2 NOISE / FCC AL-602-04-902 EnoPuck CO2 WALL / FCC 12562 12563 12564 Description CO2 traffic light, RGB-LED, EnOcean 902 MHz / FCC; Desk version; Multi-sensor for CO2, humidity, temperature, vibration, PIR; Supply voltage 12 V DC (+/-%), dimensions 100 x 28 mm, PC white opaque; incl.
EnoPuck® CO2 / CO2 NOISE / CO2 WALL Product manual Page 31 of 32 List of tables Table 1: Product functions ....................................................................................................13 Table 2: Technical data / communication .............................................................................17 Table 3: Technical data CO2 ................................................................................................17 Table 4: Technical data RH ..........................
EnoPuck® CO2 / CO2 NOISE / CO2 WALL Product manual Page 32 of 32 12 Revision history Version 1.00 Author Lehzen Reviewer Pohl Date 4.11.2022 Major changes Initial release 1.01 Lehzen Pohl 21.11.2022 Changed FCC/IC device data and device label contents (chapter 8) 1.02 Lehzen Pohl 23.11.