Product Info
Table Of Contents
- 1 Validity of this documentation
- 2 Intended use
- 3 Disposal
- 4 Device description
- 5 Technical data
- 6 Functional description in detail
- Occupancy sensor with supply voltage monitor (PIR, Vibration)
- EURID
- 7 Service / changing batteries
- 8 Safety remarks
- 9 Device labels
- 10 FCC (United States) Regulatory Statement
- 11 ISED Regulatory Statement
- 12 Dimensions / drawings
- 13 Ordering information
- 14 Revision history

AL-602-03-902 EnoPuck BASIC
Product manual Page 11 of 19
© DEUTA Controls GmbH Paffrather Str. 140, 51465 Bergisch Gladbach Tel.:+49 2202 285 57- 61
06.07.2021 Hauptstraße 76, 32479 Hille Tel: +49 5734 51466 - 0
Technical data might change info@deuta-controls.de; www.deuta-controls.dnet Fax:+49 5734 51466 - 28
6.2 Table of supported EEP’s (EnOcean Equipment Profiles)
6.2.1 Transmit / TX
The EnOcean wireless standard defines so called EnOcean Equipment Profiles
(EEP). Each EnOcean based product sends and receives data according to at least
one standardized data format. The EnoPuck BASIC transmits data described as
follows:
Cons. nr.
EEP
Description
Tx-ID
1 A5-07-01
Occupancy sensor with supply voltage
monitor (PIR, Vibration)
EURID
Table 11: Technical data / EnOcean EEP for tx
The following table describes in detail data send by the EnoPuck BASIC according to
the EEP A5-07-01:
Offset Size Bitrange Data Shortcut Description Valid
range
Scale Unit
0 8 DB3.7…DB3.0 Supply
voltage
SVC Battery
voltage
0..250 0…5.0
V
8 8 DB2.7…DB2.0 Not used (= 0)
16 8 DB1.7…DB1.0 PIR
Status
PIRS PIR Status s. Table 13 below