Specifications

6
SECTION 2
OPERATION
2.1) ADJUSTMENTS AND START-UP
CAUTION
The boiler must be filled with water and all air
purged from the system, before turning on the
power.
CAUTION
If the power is turned on before the boiler is filled
with water, the elements will become seriously
damaged.
1. Adjust the setpoint of the boiler on the electronic control. See
control section for adjustments.
2. Turn on the power, set the thermostat at 30C (85F). The
circulator; The circulator should start as well as the electrical
elements in sequence with a 15 seconds delay;
3. The circulator stays on for as long as there is a call for heat
except if differently configured on the electronic control.
2.2) MECHANICAL HIGH LIMIT
Mechanical High Limit Control
The mechanical limit aquastat must be set 20
o
F above the setpoint
temperature on the electronic control.
2.3) ELECTRONIC CONTROL
Electronic control display
On the Figure 4, description of all possible displays on the electronic control is shown.
Figure 4 : Electronic control display
In normal mode, when a key is pressed, the backlight comes blue. The backlight shade off after few seconds of inactivity on key pad.
In alarm mode, the backlight flashes green and the alarm code is displayed. See alarm section for details.
In normal operation mode, the electronic control displays alternatively the boiler temperature, the exterior temperature and the target temperature.