This chart explains the procedure for performing a Battery Test.
If a power failure occurs, your control panel has a built-in battery that will continue to power the control panel for many hours.
The control panel automatically recharges the battery when power is restored.
In addition to an automatic battery test performed every 2 minutes, the battery may also be tested manually.
This test also uses the battery to manually activate all the system sounders for 2 seconds ([PIN] [#] [8] [5] only).
If the battery voltage is low, a battery fault will occur (see Error Displays).
Testing your System (continued)
* = If this test is performed from a Master keypad, it must be in Single Partition Mode.
What will Happen
Command
Sequence
[PIN] + [#] [8] [5]
Type of
Test
Local
Battery/
Sounder Test*
What to Do
If test fails, the control panel will indicat
e
a control problem. See
Error Displays.
If power in your building has been off
recently, wait 2 hours for the battery
to recharge and then try again.
[PIN] + [System Reset]
Battery
Test
All keypad Lights will turn on.
The keypad sounder and all alarm
sounding devices will operate for 2
seconds.
The control will perform a Battery Test.
The control will report a Low Battery or
a Low Battery Restoral if necessary.