User`s guide

Page 44 P/N 39818D Copyright © 2001 Detection Systems, Inc. DS7080iP-32 Reference Guide
AC Failure Report (Program Address 079, digits 5 & 6) must be
programmed.
Open Report (Program Addresses 011, digit 1, and 078, digits 1
& 2) must be programmed.
Close Report (Program Addresses 011, digit 1, and 078, digits 3
& 4) must be programmed.
24-Hour Check-In Reports (Program Addresses 082, digits 1-4
and 024, all digits) must be programmed.
2. Timer Programming:
Bell Cutoff Times (Program Address 010, digits 10-15) must be
programmed for not less than 15 minutes.
Entry, Exit Delay Times (Program Address 010, digits 1-9) must
be programmed for not longer than 60 seconds.
3. General Control Programming:
Program Address 002, digit 2, must be programmed for Closing
Ringback and digit 3 must be programmed for no swinger shunts.
Program Address 002, Force Arming Limit, must be programmed
as: digits 8 & 9 = 0.
Program Address 008, digit 2, must be programmed for the
Commercial mode (digit 2 = 0).
4. Zone Programming:
The Burglar alarm output signal must be steady.
5. Alarm Output Programming:
Alarm Output, Program Address 009, digit 1 must be programmed
as *0 (A).
10.3.4 Police Station Connection
The control must be installed in accordance with UL Standards
UL611 and UL681 for all grades of service.
A. Grades AA and A Installations using the Applied Spectrum
PAL200 and the DACT
Required Accessories:
The control must be installed in a Detection Systems’ model
AE7080CC enclosure with a cover actuated tamper switch
installed.
The Applied Spectrum PAL200.
The Spectrum PAL200 must be installed within 3 feet of the control
and the wiring control must be in conduit.
The Applied Spectrum PAL200 inputs should be connected to
the alarm outputs (the active alarm sounder output may be used).
1. Report Programming:
Programming shall be enabled to allow all alarm signals to be
transmitted via the DACT and PAL200.
Burglar Zone Reports are not required since the alarms are
transmitted over the PAL200.
Low Battery Report (Program Address 079, digits 1 & 2) must be
programmed.
AC Failure Report (Program Address 079, digits 5 & 6) must be
programmed.
Open Report (Program Addresses 011, digit 1, and 078, digits 1
& 2) must be programmed.
Close Report (Program Addresses 011, digit 1, and 078, digits 3
& 4) must be programmed.
24-Hour Check-In Reports (Program Addresses 082, digits 1-4,
024 and 025, all digits) must be programmed.
2. Timer Programming:
Entry, Exit Delay Times (Program Address 010, digits 1-9) must
be programmed for not longer than 60 seconds.
3. General Control Programming:
Program Address 002, digit 2, must be programmed for Closing
Ringback and digit 3 must be programmed for no swinger shunts.
Program Address 002, Force Arming Limit, must be programmed
as: digits 8 & 9 = 0.
Program Address 008, digit 2, must be programmed for the
Commercial mode (digit 2 = 0).
4. Zone Programming:
The Burglar alarm output signal must be steady.
5. Alarm Output Programming:
Alarm Output, Program Address 009, digit 1 must be programmed
as *0 (A).
B. Grade A Installations using Digital Alarm Communicator
Transmitter with local bell
Required Accessories:
The control must be installed in a Detection Systems’ model
AE7080CC enclosure with a cover actuated tamper switch
installed.
The Ademco Model AB-12 bell/housing (see Section 10.4).
1. Report Programming:
Burglar Zone Reports must be programmed for those zones used.
Low Battery Report (Program Address 079, digits 1 & 2) must be
programmed.
AC Failure Report (Program Address 079, digits 5 & 6) must be
programmed.
Open Report (Program Addresses 011, digit 1, and 078, digits 1
& 2) must be programmed.
Close Report (Program Addresses 011, digit 1, and 078, digits 3
& 4) must be programmed.
24-Hour Check-In Reports (Program Addresses 082, digits 1-4,
024 and 025, all digits) must be programmed.
2. Timer Programming:
Bell Cutoff Times (Program Address 010, digits 10-15) must be
programmed for not less than 15 minutes.
Entry, Exit Delay Times (Program Address 010, digits 1-9) must
be programmed for not longer than 60 seconds.
3. General Control Programming:
Program Address 002, digit 2, must be programmed for Closing
Ringback and digit 3 must be programmed for no swinger shunts.
Program Address 002, Force Arming Limit, must be programmed
as: digits 8 & 9 = 0.
Program Address 008, digit 2, must be programmed for the
Commercial mode (digit 2 = 0).
4. Zone Programming:
The Burglar alarm output signal (whether pulsed or steady) must
be different from the Fire alarm signal.
5. Alarm Output Programming:
Alarm Output, Program Address 009, digit 1 must be programmed
as *0 (A).