User`s guide

DS7080iP-32 Reference Guide Copyright © 2001 Detection Systems, Inc. P/N 39818D Page 31
9.20 Address 025 - Auto Test / Remote Programmer Call-Out Time
If “Send a Test report every hour” was selected in Address 024, setting the “Auto Test Call-Out Hour/Minute will have no affect on
the call out time. The hourly Auto Test will occur within a few minutes after the start of each hour as defined by the panel’s date
and time set in the master user menu.
This feature requires the panel’s date and time to be set.
9.21 Address 026 - AC Report Delay
The AC Failure report can be programmed to delay for up to 255 minutes (the restoral report can also be delayed up to 255 minutes).
- If another report is sent during this delay period, the AC Fail report will be sent along with this report.
- If the AC power restores during this delay period, the AC Fail report will not be sent.
9.22 Address 027 - History Controls
History Controls determines what events are stored in the panel’s event history.
9.23 Address 028 - Special Keys
This address is used to determine the alarm output when the emergency keys are pressed.
DEFAULT
FIRE KEY [A]
SPECIAL EMERGENCY KEY [B]
PANIC KEY [C]
000
0 = Disabled
1 = Invisible
2 = Steady Audible
3 = Pulsing Audible
On
No
Entry
System
Reset
Bypass
Perimeter
Only
Off
321
654
987
#0
*
Fire
Armed
Status
1
2
3
4
5
6
Power
TEST WEEKLY
ABC
Arme d
Status
Power
Fir e
123
456
789
0
*
#
On
No
Entry
System
Reset
Bypass
Only
Perime ter
Off
ABC
Armed
Status
Power
Fire
Perimet er
Supervi sory
Bell Silenced
Trouble
12345678
123
456
789
0
*
#
On
No
Entry
System
Res et
Bypass
Only
Perimeter
Off
ABC
The Fire key is disabled if programmed as invisible.