9.1 Address 001 - EX8 Zone Expansion Module Control
This Address determines how many EX8 Zone Expansion Modules are in the system and the zone response time for those zones. There
are 8 hard-wired zones on each Zone Expansion Module. The modules need to be enabled in ascending order from Module 1 to Module
3.
Programming the EX8 Expansion Module:
Module 1 is fixed at Option Bus Address 101 and makes zones 9 through
16 available to the system.
Modules 2 and 3 are likewise fixed at Option Bus Addresses 102 and 103
respectively. They make zones 17 through 24 and 25 through 32 available
to the system.
Refer to the EX8 Installation Guide (P/N 39565) to configure the module
addresses.
Module 1 must be enabled before Module 2 can be used. Likewise, Module
2 must be enabled before Module 3 can be used.
Be sure and set each module with a different address. Failure to do so will
result in improper communication between the EX8 and the panel.
9.2 Address 002 - General Control
General Control is used to define the following functions:
Siren on Comm. Failure: If programmed, a silent zone will sound the alarm
outputs if the zone is in an alarm condition and the system fails to
communicate with the central station.
Closing Ring-Back: If programmed, the keypad sounders and Bell will
activate for 2 seconds after the system is armed and the closing report is
successfully sent. This requires the Closing Ring-Back and Closing Reports
to be programmed.
Swinger Shunt: If selected, a zone can only alarm or trouble up to three
times per armed period. After the third alarm or trouble, the zone will be
bypassed and a bypass report for this zone will be sent.
60Hz/50Hz: The selection is used to determine the primary line frequency
for the control panel.
60 Hz is required for U.L. Listed Requirements.
Allow All Arming Levels: This selection will allow Perimeter, Perimeter
Instant and Maximum Security Arming.
Enable/Disable Partitioning: Determines if the system is a one or two
partition system.
Zone Restore: This selection is used to determine when a zone restores.
- Restore when Sounders Silence: If selected, a zone sends a restoral
report and is ready to activate again only after the burglary bell cut-off
time expires or the bells are silenced.
- Restore when Zone Restores: If selected, a zone sends a restoral report
and is ready to activate again as soon as it physically restores.
- Restore when System is Disarmed: If selected, a zone sends a restoral
report when the system is disarmed. If Restore when System is Disarmed
is selected, only one alarm per zone (except fire zones) will be sent during
an armed period.
Force Arming Limit: Determines the maximum number of zones that may be force armed.