User guide

DS7060 User Guide Copyright © 1996-97 Detection Systems, Inc. Page 11
WARNING: If the bells and sirens are on and/or the red Armed light is flashing, then the keypad is signaling that an alarm has occurred
sometime before your arrival. The DS7447 will display “Zone Alarm. The DS7443 or DS7445 zone LEDs will be flashing for the
corresponding zone that is in alarm.
The keypad will also issue a pulsed tone during the entry delay instead of the usual steady tone.
If the alarm has not been previously investigated, do not enter the building unless accompanied by the appropriate Emergency Services’
personnel.
This chart explains proper procedures for disarming and/or silencing alarms.
Turning Off (disarming) the System under Duress
A duress code is used when someone demands, by threatening your life or well-being, that the system be turned off. When used, the code will
both turn off the system and report a silent duress alarm if connected to a monitoring service. User code 14 can be optionally configured as a
duress code. User code 14 will not arm the system, or report duress, if the system is not armed. Extreme care should be used when entering
your PIN to turn off the system, so a duress code is not inadvertently entered. User Code 14 is not a duress code by default. You must program
the control panel that User Code 14 is the duress code. Ask your installation company if you desire this feature.
Page 22
** = Battery Trouble and Communicator Err displays must be cleared by the [System Reset] command sequence even after the problem has
been remedied. These displays will not self clear. All the other error displays will self clear from the keypads once the problem has been
remedied.
1. DS7447 - “AC Power Failure”
DS7443 or DS7445 - LED 1 turns on steady
There is a power failure and the panel is operating on backup battery.
2. DS7447 - “Battery Trouble”
DS7443 or DS7445 - LED 2 turns on steady
If the system has just been through a power failure, wait at least two hours for the battery to recharge, then enter a PIN + [System Reset] to
perform a battery test.
3. DS7447 - “Communicator Err”
DS7443 or DS7445 - LED 3 turns on steady
The communicator failed to communicate with the central station.
4. DS7447 - “System Fault”
DS7443 or DS7445 - LED 4 turns on steady
Internal error in the control circuitry or optional circuitry. These system faults are: Ram Fault, ROM Fault, EEPROM Fault.
5. DS7447 - “Keypad Fault”
DS7443 or DS7445 - LED 5 turns on steady
One of the keypads is not responding to the control panel.
6. DS7447 - “Aux Power Fault”
DS7443 or DS7445 - LED 6 turns on steady
The auxiliary power has been shorted.
7. DS7447 - “Zone Trouble”
DS7443 or DS7445 - LED of the zone in trouble will light
One of the zones is not responding to the control panel. This may also be displayed during power-up (if so, ignore).